Service Diagnosis
87
4.10 Compressor Lock
Remote Control
Display
E6
Method of
Malfunction
Detection
A compressor lock is detected by checking the compressor running condition through the
position detection circuit.
Malfunction
Decision
Conditions
20/25 class
Operation stops due to overcurrent.
If the error repeats 16 times, the system is shut down.
Reset condition: Continuous run for about 11 minutes without any other error
35 class
A compressor lock is detected by the current waveform generated when applying high-
frequency voltage to the motor.
If the error repeats 16 times, the system is shut down
Reset condition: Continuous run for about 5 minutes without any other error
Supposed
Causes
Compressor locked
Compressor harness disconnected
Troubleshooting
Turn off the power. Disconnect the
harnesses U, V, and W.
(R8399)
Caution
NO
YES
YES
NO
NO
YES
Check with the inverter checker (
∗
).
Turn off the power and reconnect
the harnesses. Turn on the power
again and restart the system.
(Precaution before turning on the power again)
Make sure the power has been off for at least 30 seconds.
Correct the power supply or
replace the PM1.
(Replace the outdoor unit
PCB.)
∗
Inverter checker
Part No.: 1225477
Replace the compressor.
Replace it as required.
Replace the compressor.
Check the electronic
expansion valve.
Normal?
Emergency stop
without compressor running?
System shut
down after errors repeated
several times?
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
SIENBE04-925_A_FRONT.pdf 102
24/02/2011 13:53:56
Содержание RXL25G2V1B
Страница 8: ...SiENBE04 925_A vi Table of Contents ...
Страница 14: ...Introduction SiENBE04 925_A xii ...
Страница 15: ...SiENBE04 925_A List of Functions 1 Part 1 List of Functions 1 Functions 2 ...
Страница 17: ...SiENBE04 925_A Specifications 3 Part 2 Specifications 1 Specifications 4 ...
Страница 20: ...Specifications SiENBE04 925_A 6 Specifications ...
Страница 186: ...SiENBE04 925_A Outdoor Unit RXL20G2V1B Removal Procedure 171 4 Feature of the thermistors Step Procedure Points R9356 ...