Main Functions
SiENBE04-925_A
30
Function and Control
2. Motions (for example: in cooling)
When the microcomputer does not have a signal from the sensor in 20 minutes, it judges
that nobody is in the room and operates the unit in temperature shifted from the target
temperature. (Cooling / Dry : 2°C higher, Heating : 2°C lower, Auto : according to the
operation mode at that time.)
H
1 In case of FAN mode, the fan speed reduces by 60 rpm.
3. Airflow direction in 2-area INTELLIGENT EYE operation
Detection method: The opposite area of detected area is set as the target direction.
1. Detection signal ON in both area A and B: Shift the airflow direction to area B (left side)
2. Detection signal ON in area A: Shift the airflow direction to area B (left side)
3. Detection signal ON in area B: Shift the airflow direction to area A (right side)
4. Detection signal OFF in both area A and B: No change
* When the detection signal is OFF for 20 minutes in both area A and B, the unit starts energy
saving operation.
Others
For dry operation, you cannot set the temperature with remote control, but internally the
target temperature is shifted by 2°C.
ON
OFF
RESET.
(From area A or B)
20 min.
20 min.
ON
OFF
ON
OFF
Operation
OFF
Fan speed (
H
1)
Set speed
Set speed
Target temperature
(R12183)
Remote control
INTELLIGENT EYE
button
ON
OFF
INTELLIGENT EYE
lamp
Human detection
signal
within 20
minutes
Top view
Wall
Indoor unit
Area A
Area B
Left
Right
Human
(R3853)
SIENBE04-925_A_FRONT.pdf 44
24/02/2011 13:53:52
Содержание RXL25G2V1B
Страница 8: ...SiENBE04 925_A vi Table of Contents ...
Страница 14: ...Introduction SiENBE04 925_A xii ...
Страница 15: ...SiENBE04 925_A List of Functions 1 Part 1 List of Functions 1 Functions 2 ...
Страница 17: ...SiENBE04 925_A Specifications 3 Part 2 Specifications 1 Specifications 4 ...
Страница 20: ...Specifications SiENBE04 925_A 6 Specifications ...
Страница 186: ...SiENBE04 925_A Outdoor Unit RXL20G2V1B Removal Procedure 171 4 Feature of the thermistors Step Procedure Points R9356 ...