Control Specification
SiENBE04-925_A
34
Function and Control
3. Control Specification
3.1
Mode Hierarchy
Outline
There are two modes; the one is the normal operation mode and the other is the forced
operation mode for installation and providing service.
Detail
There are following modes; stop, cooling (includes drying), heating (include defrosting)
Note:
Unless specified otherwise, an indoor dry operation command is regarded as cooling operation.
Air conditioner control mode
Forced operating mode
Forced cooling (for Pump Down Operation)
Normal operating mode
Cooling
Heating
Defrosting
Stop mode (except for cooling/heating modes by indoor command)
Preheating operation
During C (capacitor) is discharging
Stop
(R2829)
SIENBE04-925_A_FRONT.pdf 48
24/02/2011 13:53:52