Table 503:
3PHSUM Output signals
Name
Type
Description
AI3P
GROUP SIGNAL
Linear combination of two connected three phase
inputs
AI1
GROUP SIGNAL
Linear combination of input 1 signals from both
SMAI blocks
AI2
GROUP SIGNAL
Linear combination of input 2 signals from both
SMAI blocks
AI3
GROUP SIGNAL
Linear combination of input 3 signals from both
SMAI blocks
AI4
GROUP SIGNAL
Linear combination of input 4 signals from both
SMAI blocks
17.10.5
Settings
Table 504:
3PHSUM Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
GlobalBaseSel
1 - 6
-
1
1
Selection of one of the Global Base Value
groups
SummationType
Group2
Group1-Group2
Group2-Group1
-(Group2)
-
-
Group2
Summation type
DFTReference
InternalDFTRef
DFTRefGrp1
External DFT ref
-
-
InternalDFTRef
DFT reference
Table 505:
3PHSUM Non group settings (advanced)
Name
Values (Range)
Unit
Step
Default
Description
FreqMeasMinVal
5 - 200
%
1
10
Amplitude limit for frequency calculation in
% of Ubase
17.10.6
Operation principle
Summation block 3 phase 3PHSUM receives the three-phase signals from Signal
matrix for analog inputs function (SMAI). In the same way, the BLOCK input will
reset all the outputs of the function to 0.
17.11
Global base values GBASVAL
Section 17
1MRK 504 135-UEN A
Basic IED functions
590
Technical manual
Содержание ret650
Страница 1: ...Relion 650 series Transformer protection RET650 Technical manual ...
Страница 2: ......
Страница 40: ...34 ...
Страница 62: ...56 ...
Страница 84: ...78 ...
Страница 208: ...202 ...
Страница 353: ...Table 236 Gray code conversion IEC06000523 V1 EN 1MRK 504 135 UEN A Section 12 Control 347 Technical manual ...
Страница 376: ...370 ...
Страница 414: ...408 ...
Страница 530: ...524 ...
Страница 562: ...556 ...
Страница 620: ...614 ...
Страница 668: ...662 ...
Страница 669: ...663 ...