the fact that at least one user has tried to log on wrongly into the IED and it was
blocked (the output USRBLKED)
•
the fact that at least one user is logged on (the output LOGGEDON)
Whenever one of the two events occurs, the corresponding output (USRBLKED or
LOGGEDON) is activated.
17.16
Denial of service
17.16.1
Functionality
The Denial of service functions (DOSLAN1 and DOSFRNT) are designed to limit
overload on the IED produced by heavy Ethernet network traffic. The communication
facilities must not be allowed to compromise the primary functionality of the device.
All inbound network traffic will be quota controlled so that too heavy network loads
can be controlled. Heavy network load might for instance be the result of
malfunctioning equipment connected to the network.
17.16.2
Denial of service, frame rate control for front port DOSFRNT
17.16.2.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Denial of service, frame rate control for
front port
DOSFRNT
-
-
17.16.2.2
Function block
DOSFRNT
LINKUP
WARNING
ALARM
IEC09000133-1-en.vsd
IEC09000133 V1 EN
Figure 264:
DOSFRNT function block
17.16.2.3
Signals
Table 511:
DOSFRNT Output signals
Name
Type
Description
LINKUP
BOOLEAN
Ethernet link status
WARNING
BOOLEAN
Frame rate is higher than normal state
ALARM
BOOLEAN
Frame rate is higher than throttle state
1MRK 504 135-UEN A
Section 17
Basic IED functions
597
Technical manual
Содержание ret650
Страница 1: ...Relion 650 series Transformer protection RET650 Technical manual ...
Страница 2: ......
Страница 40: ...34 ...
Страница 62: ...56 ...
Страница 84: ...78 ...
Страница 208: ...202 ...
Страница 353: ...Table 236 Gray code conversion IEC06000523 V1 EN 1MRK 504 135 UEN A Section 12 Control 347 Technical manual ...
Страница 376: ...370 ...
Страница 414: ...408 ...
Страница 530: ...524 ...
Страница 562: ...556 ...
Страница 620: ...614 ...
Страница 668: ...662 ...
Страница 669: ...663 ...