percent of the global parameter
UBase
. To avoid oscillations of the output START
signal, a hysteresis has been included.
START
START
TRIP
Start
&
Trip
Output
Logic
Definite Time Delay
TimeDlyOperate
BLOCK
IEC09000033-1.vsd
Frequency
Comparator
f > StartFrequency
TRIP
BLKDMAGN
BLOCK
OR
freqNotValid
IEC09000033 V1 EN
Figure 106:
Schematic design of overfrequency protection SAPTOF
10.2.7.2
Time delay
The time delay for SAPTOF is a settable definite time delay, specified by the setting
tDelay
.
If the START condition frequency ceases during the delay time, and is not fulfilled
again within a defined reset time, the START output is reset.
10.2.7.3
Blocking
It is possible to block Over frequency protection (SAPTOF) completely, by binary
input signals or by parameter settings, where:
BLOCK:
blocks all outputs
If the measured voltage level decreases below the setting of
MinValFreqMeas
in the
preprocessing function both the START and the TRIP outputs are blocked.
10.2.7.4
Design
The design of overfrequency protection SAPTOF is schematically described in
figure
1MRK 504 135-UEN A
Section 10
Frequency protection
237
Technical manual
Содержание ret650
Страница 1: ...Relion 650 series Transformer protection RET650 Technical manual ...
Страница 2: ......
Страница 40: ...34 ...
Страница 62: ...56 ...
Страница 84: ...78 ...
Страница 208: ...202 ...
Страница 353: ...Table 236 Gray code conversion IEC06000523 V1 EN 1MRK 504 135 UEN A Section 12 Control 347 Technical manual ...
Страница 376: ...370 ...
Страница 414: ...408 ...
Страница 530: ...524 ...
Страница 562: ...556 ...
Страница 620: ...614 ...
Страница 668: ...662 ...
Страница 669: ...663 ...