Operating sequence
The operation mode is set individually for each output, either
OFF
,
TOGGLE
or
PULSED
.
Setting OFF
This mode always gives the output the value. A change of the input value does not
affect the output value.
Input value
Output value
IEC09000330-1-en.vsd
IEC09000330 V1 EN
Figure 26:
Sequence diagram for setting OFF
Setting TOGGLE
In this mode the output toggles each time the function block detects that the input has
been written (the input has completed a pulse). Note that the input attribute is reset
each time the function block executes. The function block execution is marked with
a dotted line below.
Input value
Output value
IEC09000331_1_en.vsd
IEC09000331 V1 EN
Figure 27:
Sequence diagram for setting TOGGLE
Setting PULSED
In this mode the output will be high for as long as the setting
pulse time
. After this time
the output will go back to 0. The input attribute is reset when the function block detects
it being high and there is no output pulse.
Note that the third positive edge on the input attribute does not cause a pulse, since the
edge was applied during pulse output. A new pulse can only begin when the output is
zero; else the trigger edge is lost.
Section 5
1MRK 504 135-UEN A
Local Human-Machine-Interface LHMI
76
Technical manual
Содержание ret650
Страница 1: ...Relion 650 series Transformer protection RET650 Technical manual ...
Страница 2: ......
Страница 40: ...34 ...
Страница 62: ...56 ...
Страница 84: ...78 ...
Страница 208: ...202 ...
Страница 353: ...Table 236 Gray code conversion IEC06000523 V1 EN 1MRK 504 135 UEN A Section 12 Control 347 Technical manual ...
Страница 376: ...370 ...
Страница 414: ...408 ...
Страница 530: ...524 ...
Страница 562: ...556 ...
Страница 620: ...614 ...
Страница 668: ...662 ...
Страница 669: ...663 ...