Table 499:
SMAI_20_1 Non group settings (advanced)
Name
Values (Range)
Unit
Step
Default
Description
Negation
Off
NegateN
Negate3Ph
NeN
-
-
Off
Negation
MinValFreqMeas
5 - 200
%
1
10
Limit for frequency calculation in % of
UBase
Even if the
AnalogInputType
setting of a SMAI block is set to
Current
, the
MinValFreqMeas
setting is still visible. This means that
the minimum level for current amplitude is based on
UBase
. For
example, if
UBase
is 20000, the minimum amplitude for current is
20000 * 10% = 2000. This has practical affect only if the current
measuring SMAI is used as a frequency reference for the adaptive
DFT. This is not recommended, see the Setting guidelines.
Table 500:
SMAI_20_12 Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
GlobalBaseSel
1 - 6
-
1
1
Selection of one of the Global Base Value
groups
DFTReference
InternalDFTRef
DFTRefGrp1
DFTRefGrp2
DFTRefGrp3
DFTRefGrp4
DFTRefGrp5
DFTRefGrp6
DFTRefGrp7
DFTRefGrp8
DFTRefGrp9
DFTRefGrp10
DFTRefGrp11
DFTRefGrp12
External DFT ref
-
-
InternalDFTRef
DFT reference
ConnectionType
Ph-N
Ph-Ph
-
-
Ph-N
Input connection type
AnalogInputType
Voltage
Current
-
-
Voltage
Analog input signal type
Table 501:
SMAI_20_12 Non group settings (advanced)
Name
Values (Range)
Unit
Step
Default
Description
Negation
Off
NegateN
Negate3Ph
NeN
-
-
Off
Negation
MinValFreqMeas
5 - 200
%
1
10
Limit for frequency calculation in % of
UBase
Section 17
1MRK 504 135-UEN A
Basic IED functions
584
Technical manual
Содержание ret650
Страница 1: ...Relion 650 series Transformer protection RET650 Technical manual ...
Страница 2: ......
Страница 40: ...34 ...
Страница 62: ...56 ...
Страница 84: ...78 ...
Страница 208: ...202 ...
Страница 353: ...Table 236 Gray code conversion IEC06000523 V1 EN 1MRK 504 135 UEN A Section 12 Control 347 Technical manual ...
Страница 376: ...370 ...
Страница 414: ...408 ...
Страница 530: ...524 ...
Страница 562: ...556 ...
Страница 620: ...614 ...
Страница 668: ...662 ...
Страница 669: ...663 ...