Description
Type test value
Reference
•
Continuous
100 A/m
Pulse magnetic field immunity
test
1000A/m
IEC 61000–4–9, level 5
Damped oscillatory magnetic
field
100A/m, 100 kHz and 1MHz
IEC 6100–4–10, level 5
Power frequency immunity test
IEC 60255-22-7, class A
IEC 61000-4-16
•
Common mode
300 V rms
•
Differential mode
150 V rms
Voltage dips and short
interruptionsc on DC power
supply
Dips:
40%/200 ms
70%/500 ms
Interruptions:
0-50 ms: No restart
0...∞ s : Correct behaviour at
power down
IEC 60255-11
IEC 61000-4-11
Voltage dips and interruptions
on AC power supply
Dips:
40% 10/12 cycles at 50/60 Hz
70% 25/30 cycles at 50/60 Hz
Interruptions:
0–50 ms: No restart
0...∞ s: Correct behaviour at
power down
IEC 60255–11
IEC 61000–4–11
Electromagnetic emission tests
EN 55011, class A
IEC 60255-25
ANSI C63.4, FCC
•
Conducted, RF-emission
(mains terminal)
0.15...0.50 MHz
< 79 dB(µV) quasi peak
< 66 dB(µV) average
0.5...30 MHz
< 73 dB(µV) quasi peak
< 60 dB(µV) average
•
Radiated RF-emission,
IEC
30...230 MHz
< 40 dB(µV/m) quasi peak,
measured at 10 m distance
230...1000 MHz
< 47 dB(µV/m) quasi peak,
measured at 10 m distance
Section 20
1MRK 504 135-UEN A
IED and functionality tests
622
Technical manual
Содержание ret650
Страница 1: ...Relion 650 series Transformer protection RET650 Technical manual ...
Страница 2: ......
Страница 40: ...34 ...
Страница 62: ...56 ...
Страница 84: ...78 ...
Страница 208: ...202 ...
Страница 353: ...Table 236 Gray code conversion IEC06000523 V1 EN 1MRK 504 135 UEN A Section 12 Control 347 Technical manual ...
Страница 376: ...370 ...
Страница 414: ...408 ...
Страница 530: ...524 ...
Страница 562: ...556 ...
Страница 620: ...614 ...
Страница 668: ...662 ...
Страница 669: ...663 ...