Contact check criteria can be used where the fault current through the breaker is small.
Breaker failure protection, 3-phase activation and output (CCRBRF) current criteria
can be fulfilled by one or two phase currents the residual current, or one phase current
plus residual current. When those currents exceed the user defined settings, the
function is triggered. These conditions increase the security of the back-up trip
command.
CCRBRF function can be programmed to give a three-phase re-trip of the own breaker
to avoid inadvertent tripping of surrounding breakers.
8.6.3
Function block
CCRBRF
I3P*
BLOCK
START
CBCLDL1
CBCLDL2
CBCLDL3
TRBU
TRRET
IEC09000272_1_en.vsd
IEC09000272 V1 EN
Figure 78:
CCRBRF function block
8.6.4
Signals
Table 97:
CCRBRF Input signals
Name
Type
Default
Description
I3P
GROUP
SIGNAL
-
Three phase group signal for current inputs
BLOCK
BOOLEAN
0
Block of function
START
BOOLEAN
0
Three phase start of breaker failure protection
function
CBCLDL1
BOOLEAN
1
Circuit breaker closed in phase L1
CBCLDL2
BOOLEAN
1
Circuit breaker closed in phase L2
CBCLDL3
BOOLEAN
1
Circuit breaker closed in phase L3
Table 98:
CCRBRF Output signals
Name
Type
Description
TRBU
BOOLEAN
Back-up trip by breaker failure protection function
TRRET
BOOLEAN
Retrip by breaker failure protection function
Section 8
1MRK 504 135-UEN A
Current protection
180
Technical manual
Содержание ret650
Страница 1: ...Relion 650 series Transformer protection RET650 Technical manual ...
Страница 2: ......
Страница 40: ...34 ...
Страница 62: ...56 ...
Страница 84: ...78 ...
Страница 208: ...202 ...
Страница 353: ...Table 236 Gray code conversion IEC06000523 V1 EN 1MRK 504 135 UEN A Section 12 Control 347 Technical manual ...
Страница 376: ...370 ...
Страница 414: ...408 ...
Страница 530: ...524 ...
Страница 562: ...556 ...
Страница 620: ...614 ...
Страница 668: ...662 ...
Страница 669: ...663 ...