Name of signal
Reasons for activation
Time Synch Error
This signal will be active when the source of the time
synchronization is lost, or when the time system has to make
a time reset.
Runtime Exec Error
This signal will be active if the Runtime Engine failed to do
some actions with the application threads. The actions can
be loading of settings or parameters for components,
changing of setting groups, loading or unloading of
application threads.
IEC61850 Error
This signal will be active if the IEC 61850 stack did not
succeed in some actions like reading IEC 61850
configuration, startup, for example.
SW Watchdog Error
This signal will be activated when the IED has been under too
heavy load for at least 5 minutes. The operating systems
background task is used for the measurements.
Runtime App Error
This signal will be active if one or more of the application
threads are not in the state that Runtime Engine expects. The
states can be CREATED, INITIALIZED, RUNNING, for
example.
Setting(s) Changed
This signal will generate an internal event to the internal
event list if any setting(s) is changed.
Setting Group(s) Changed
This signal will generate an internal event to the Internal
Event List if any setting group(s) is changed.
Change Lock
This signal will generate an internal Event to the Internal
Event List if the Change Lock status is changed
File System Error
This signal will be active if both the working file and the
backup file are corrupted and cannot be recovered.
DNP3 Error
This signal will be active when DNP3 detects any
configuration error during startup.
17.1.4.2
Run-time model
The analog signals to the A/D converter is internally distributed into two different
converters, one with low amplification and one with high amplification, see
Section 17
1MRK 504 135-UEN A
Basic IED functions
562
Technical manual
Содержание ret650
Страница 1: ...Relion 650 series Transformer protection RET650 Technical manual ...
Страница 2: ......
Страница 40: ...34 ...
Страница 62: ...56 ...
Страница 84: ...78 ...
Страница 208: ...202 ...
Страница 353: ...Table 236 Gray code conversion IEC06000523 V1 EN 1MRK 504 135 UEN A Section 12 Control 347 Technical manual ...
Страница 376: ...370 ...
Страница 414: ...408 ...
Страница 530: ...524 ...
Страница 562: ...556 ...
Страница 620: ...614 ...
Страница 668: ...662 ...
Страница 669: ...663 ...