8.3.6
Monitored data
Table 83:
EFPIOC Monitored data
Name
Type
Values (Range)
Unit
Description
IN
REAL
-
A
Residual current
8.3.7
Operation principle
The sampled analog residual currents are pre-processed in a discrete Fourier filter
(DFT) block. From the fundamental frequency components of the residual current, as
well as from the sample values the equivalent RMS value is derived. This current
value is fed to the Instantaneous residual overcurrent protection (EFPIOC). In a
comparator the RMS value is compared to the set operation current value of the
function (
IN>>
). If the residual current is larger than the set operation current a signal
from the comparator is set to true. This signal will, without delay, activate the output
signal TRIP.
8.3.8
Technical data
Table 84:
EFPIOC technical data
Function
Range or value
Accuracy
Operate current
(1-2500)% of lBase
±
1.0% of I
r
at I
£
I
r
±
1.0% of I at I > I
r
Reset ratio
> 95%
-
Operate time
20 ms typically at 0 to 2 x I
set
-
Reset time
30 ms typically at 2 to 0 x I
set
-
Critical impulse time
10 ms typically at 0 to 2 x I
set
-
Operate time
10 ms typically at 0 to 5x I
set
-
Reset time
40 ms typically at 5 to 0x I
set
-
Critical impulse time
2 ms typically at 0 to 5 x I
set
-
Dynamic overreach
< 5% at
t
= 100 ms
-
8.4
Four step residual overcurrent protection, zero,
negative sequence direction EF4PTOC
Section 8
1MRK 504 135-UEN A
Current protection
154
Technical manual
Содержание ret650
Страница 1: ...Relion 650 series Transformer protection RET650 Technical manual ...
Страница 2: ......
Страница 40: ...34 ...
Страница 62: ...56 ...
Страница 84: ...78 ...
Страница 208: ...202 ...
Страница 353: ...Table 236 Gray code conversion IEC06000523 V1 EN 1MRK 504 135 UEN A Section 12 Control 347 Technical manual ...
Страница 376: ...370 ...
Страница 414: ...408 ...
Страница 530: ...524 ...
Страница 562: ...556 ...
Страница 620: ...614 ...
Страница 668: ...662 ...
Страница 669: ...663 ...