Name
Type
Description
QC5REL
BOOLEAN
Switching of QC5 is allowed
QC5ITL
BOOLEAN
Switching of QC5 is forbidden
QB2OPTR
BOOLEAN
QB2 is in open position
QB2CLTR
BOOLEAN
QB2 is in closed position
VPQB2TR
BOOLEAN
Switch status of QB2 is valid (open or closed)
Table 218:
DB_LINE Output signals
Name
Type
Description
QB9REL
BOOLEAN
Switching of QB9 is allowed
QB9ITL
BOOLEAN
Switching of QB9 is forbidden
QC3REL
BOOLEAN
Switching of QC3 is allowed
QC3ITL
BOOLEAN
Switching of QC3 is forbidden
QC9REL
BOOLEAN
Switching of QC9 is allowed
QC9ITL
BOOLEAN
Switching of QC9 is forbidden
12.2.6.6
Settings
The function does not have any settings available in Local HMI or Protection and
Control IED Manager (PCM600).
12.2.7
Interlocking for line bay ABC_LINE
12.2.7.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Interlocking for line bay
ABC_LINE
-
3
12.2.7.2
Functionality
The interlocking for line bay (ABC_LINE) function is used for a line connected to a
double busbar arrangement with a transfer busbar according to figure
. The
function can also be used for a double busbar arrangement without transfer busbar or
a single busbar arrangement with/without transfer busbar.
1MRK 504 135-UEN A
Section 12
Control
311
Technical manual
Содержание ret650
Страница 1: ...Relion 650 series Transformer protection RET650 Technical manual ...
Страница 2: ......
Страница 40: ...34 ...
Страница 62: ...56 ...
Страница 84: ...78 ...
Страница 208: ...202 ...
Страница 353: ...Table 236 Gray code conversion IEC06000523 V1 EN 1MRK 504 135 UEN A Section 12 Control 347 Technical manual ...
Страница 376: ...370 ...
Страница 414: ...408 ...
Страница 530: ...524 ...
Страница 562: ...556 ...
Страница 620: ...614 ...
Страница 668: ...662 ...
Страница 669: ...663 ...