17.2
Time synchronization
17.2.1
Functionality
The time synchronization source selector is used to select a common source of
absolute time for the IED when it is a part of a protection system. This makes it
possible to compare event and disturbance data between all IEDs in a station
automation system.
Micro SCADA OPC server should not be used as a time
synchronization source.
17.2.2
Time synchronization TIMESYNCHGEN
17.2.2.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Time synchronization
TIMESYNCHGE
N
-
-
17.2.2.2
Settings
Table 477:
TIMESYNCHGEN Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
CoarseSyncSrc
Off
SNTP
DNP
IEC60870-5-103
-
-
Off
Coarse time synchronization source
FineSyncSource
Off
SNTP
IRIG-B
-
-
Off
Fine time synchronization source
SyncMaster
Off
SNTP-Server
-
-
Off
Activate IED as synchronization master
17.2.3
Time synchronization via SNTP
17.2.3.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Time synchronization via SNTP
SNTP
-
-
Section 17
1MRK 504 135-UEN A
Basic IED functions
564
Technical manual
Содержание ret650
Страница 1: ...Relion 650 series Transformer protection RET650 Technical manual ...
Страница 2: ......
Страница 40: ...34 ...
Страница 62: ...56 ...
Страница 84: ...78 ...
Страница 208: ...202 ...
Страница 353: ...Table 236 Gray code conversion IEC06000523 V1 EN 1MRK 504 135 UEN A Section 12 Control 347 Technical manual ...
Страница 376: ...370 ...
Страница 414: ...408 ...
Страница 530: ...524 ...
Страница 562: ...556 ...
Страница 620: ...614 ...
Страница 668: ...662 ...
Страница 669: ...663 ...