Table 515:
Analog input modules TRM
Terminal
TRM
6I + 4U
TRM
8I + 2U
TRM
4I + 1I + 5U
TRM
4I + 6U
X101-1, 2
1/5A
1/5A
1/5A
1/5A
X101-3, 4
1/5A
1/5A
1/5A
1/5A
X101-5, 6
1/5A
1/5A
1/5A
1/5A
X101-7, 8
1/5A
1/5A
1/5A
1/5A
X101-9, 10
1/5A
1/5A
0.1/0.5A
100/220V
X102-1, 2
1/5A
1/5A
100/220V
100/220V
X102-3, 4
100/220V
1/5A
100/220V
100/220V
X102-5, 6
100/220V
1/5A
100/220V
100/220V
X102-7, 8
100/220V
100/220V
100/220V
100/220V
X102-9, 10
100/220V
100/220V
100/220V
100/220V
Table 516:
Analog input modules AIM
Terminal
AIM
6I + 4U
AIM
4I + 1I + 5U
X103-1, 2
1/5A
1/5A
X103-3, 4
1/5A
1/5A
X103-5, 6
1/5A
1/5A
X103-7, 8
1/5A
1/5A
X103-9, 10
1/5A
0.1/0.5A
X104-1, 2
1/5A
100/220V
X104-3, 4
100/220V
100/220V
X104-5, 6
100/220V
100/220V
X104-7, 8
100/220V
100/220V
X104-9, 10
100/220V
100/220V
See the connection diagrams for information on the analog input
module variant included in a particular configured IED. The primary
and secondary rated values of the primary VT's and CT's are set for the
analog inputs of the IED.
18.2.2
Auxiliary supply voltage input
The auxiliary voltage of the IED is connected to terminals X420-1 and X420-2/3. The
terminals used depend on the power supply.
The permitted auxiliary voltage range of the IED is marked on top of the IED's LHMI.
Section 18
1MRK 504 135-UEN A
IED physical connections
602
Technical manual
Содержание ret650
Страница 1: ...Relion 650 series Transformer protection RET650 Technical manual ...
Страница 2: ......
Страница 40: ...34 ...
Страница 62: ...56 ...
Страница 84: ...78 ...
Страница 208: ...202 ...
Страница 353: ...Table 236 Gray code conversion IEC06000523 V1 EN 1MRK 504 135 UEN A Section 12 Control 347 Technical manual ...
Страница 376: ...370 ...
Страница 414: ...408 ...
Страница 530: ...524 ...
Страница 562: ...556 ...
Страница 620: ...614 ...
Страница 668: ...662 ...
Страница 669: ...663 ...