When the measured frequency returns to the level corresponding to the setting
RestoreFreq
, a 100ms pulse is given on the output RESTORE after a settable time
delay (
tRestore
).
10.1.7.3
Blocking
It is possible to block underfrequency protection SAPTUF completely, by binary
input signal:
BLOCK:
blocks all outputs
If the measured voltage level decreases below the setting of
MinValFreqMeas
in the
preprocessing function both the START and the TRIP outputs are blocked.
10.1.7.4
Design
The design of underfrequency protection SAPTUF is schematically described in
figure
.
Figure 104:
Simplified logic diagram for SAPTUF
10.1.8
Technical data
Table 158:
SAPTUF Technical data
Function
Range or value
Accuracy
Operate value, start function
(35.00-75.00) Hz
± 2.0 mHz at
symmetrical three-
phase voltage
Operate value, restore
frequency
(45 - 65) Hz
± 2.0 mHz
Reset ratio
<1.001
-
Operate time, start function
At 50 Hz: 200 ms typically at f
set
+0.5 Hz to f
set
-0.5 Hz
At 60 Hz: 170 ms typically at f
set
+0.5 Hz to f
set
-0.5 Hz
-
Reset time, start function
At 50 Hz: 60 ms typically at f
set
-0.5 Hz to f
set
+0.5 Hz
At 60 Hz: 50 ms typically at f
set
-0.5 Hz to f
set
+0.5 Hz
-
Operate time delay
(0.000-60.000)s
<250 ms
Restore time delay
(0.000-60.000)s
<150 ms
10.2
Overfrequency protection SAPTOF
Section 10
1MRK 504 135-UEN A
Frequency protection
234
Technical manual
Содержание ret650
Страница 1: ...Relion 650 series Transformer protection RET650 Technical manual ...
Страница 2: ......
Страница 40: ...34 ...
Страница 62: ...56 ...
Страница 84: ...78 ...
Страница 208: ...202 ...
Страница 353: ...Table 236 Gray code conversion IEC06000523 V1 EN 1MRK 504 135 UEN A Section 12 Control 347 Technical manual ...
Страница 376: ...370 ...
Страница 414: ...408 ...
Страница 530: ...524 ...
Страница 562: ...556 ...
Страница 620: ...614 ...
Страница 668: ...662 ...
Страница 669: ...663 ...