Table 316:
B16IFCVI Output signals
Name
Type
Description
OUT
INTEGER
Output value
13.6.5
Settings
The function does not have any parameters available in local HMI or Protection and
Control IED Manager (PCM600)
13.6.6
Monitored data
Table 317:
B16IFCVI Monitored data
Name
Type
Values (Range)
Unit
Description
OUT
INTEGER
-
-
Output value
13.6.7
Operation principle
The Boolean 16 to integer conversion with logic node representation function
(B16IFCVI) will transfer a combination of up to 16 binary inputs INx, where 1≤x≤16,
to an integer. Each INx represents a value according to the table below from 0 to
32768. This follows the general formula: INx = 2
x-1
where 1≤x≤16. The sum of all the
values on the activated INx will be available on the output OUT as a sum of the integer
values of all the inputs INx that are activated. OUT is an integer. When all INx (where
1≤x≤16) are activated, that is = Boolean 1, it corresponds to that integer 65535 is
available on the output OUT. The B16IFCVI function is designed for receiving the
integer input from a station computer - for example, over IEC 61850. If the BLOCK
input is activated, it will freeze the logical outputs at the last value.
Values of each of the different OUTx from function block B16IFCVI for 1≤x≤16.
The sum of the value on each INx corresponds to the integer presented on the output
OUT on the function block B16IFCVI.
Name of input
Type
Default
Description
Value when
activated
Value when
deactivated
IN1
BOOLEAN
0
Input 1
1
0
IN2
BOOLEAN
0
Input 2
2
0
IN3
BOOLEAN
0
Input 3
4
0
IN4
BOOLEAN
0
Input 4
8
0
IN5
BOOLEAN
0
Input 5
16
0
IN6
BOOLEAN
0
Input 6
32
0
IN7
BOOLEAN
0
Input 7
64
0
IN8
BOOLEAN
0
Input 8
128
0
IN9
BOOLEAN
0
Input 9
256
0
Table continues on next page
1MRK 504 135-UEN A
Section 13
Logic
397
Technical manual
Содержание ret650
Страница 1: ...Relion 650 series Transformer protection RET650 Technical manual ...
Страница 2: ......
Страница 40: ...34 ...
Страница 62: ...56 ...
Страница 84: ...78 ...
Страница 208: ...202 ...
Страница 353: ...Table 236 Gray code conversion IEC06000523 V1 EN 1MRK 504 135 UEN A Section 12 Control 347 Technical manual ...
Страница 376: ...370 ...
Страница 414: ...408 ...
Страница 530: ...524 ...
Страница 562: ...556 ...
Страница 620: ...614 ...
Страница 668: ...662 ...
Страница 669: ...663 ...