12.10.4
Settings
Table 265:
I103IEDCMD Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
FunctionType
1 - 255
-
1
255
Function type (1-255)
12.11
Function commands user defined for IEC
60870-5-103 I103USRCMD
12.11.1
Functionality
I103USRCMD is a command block in control direction with user defined output
signals. These function blocks include the
FunctionType
parameter for each block in
the private range, and the Information number parameter for each output signal.
12.11.2
Function block
IEC10000284-1-en.vsd
I103USRCMD
BLOCK
^OUTPUT1
^OUTPUT2
^OUTPUT3
^OUTPUT4
^OUTPUT5
^OUTPUT6
^OUTPUT7
^OUTPUT8
IEC10000284 V1 EN
Figure 160:
I103USRCMD function block
12.11.3
Signals
Table 266:
I103USRCMD Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block of commands
Table 267:
I103USRCMD Output signals
Name
Type
Description
OUTPUT1
BOOLEAN
Command output 1
OUTPUT2
BOOLEAN
Command output 2
OUTPUT3
BOOLEAN
Command output 3
OUTPUT4
BOOLEAN
Command output 4
OUTPUT5
BOOLEAN
Command output 5
Table continues on next page
Section 12
1MRK 504 135-UEN A
Control
366
Technical manual
Содержание ret650
Страница 1: ...Relion 650 series Transformer protection RET650 Technical manual ...
Страница 2: ......
Страница 40: ...34 ...
Страница 62: ...56 ...
Страница 84: ...78 ...
Страница 208: ...202 ...
Страница 353: ...Table 236 Gray code conversion IEC06000523 V1 EN 1MRK 504 135 UEN A Section 12 Control 347 Technical manual ...
Страница 376: ...370 ...
Страница 414: ...408 ...
Страница 530: ...524 ...
Страница 562: ...556 ...
Страница 620: ...614 ...
Страница 668: ...662 ...
Страница 669: ...663 ...