1. directly measured (when a dedicated VT input of the IED is connected in
PCM600 to the fourth analog input of the pre-processing block connected to
EF4PTOC function input U3P). This dedicated IED VT input shall be then
connected to open delta winding of a three phase main VT.
2. calculated from three phase voltage input within the IED (when the fourth analog
input into the pre-processing block connected to EF4PTOC analog function input
U3P is NOT connected to a dedicated VT input of the IED in PCM600). In such
case the pre-processing block will calculate 3U
0
from the first three inputs into
the pre-processing block by using the following formula:
UPol =3U0 =(UL1+UL2+UL3)
IECEQUATION2407 V1 EN
(Equation 43)
where:
UL1, UL2 and UL3
are fundamental frequency phasors of three individual phase voltages.
In order to use this, all three phase-to-earth voltages must be connected to three IED VT
inputs.
The residual voltage is pre-processed by a discrete fourier filter. Thus, the phasor of
the fundamental frequency component of the residual voltage is derived.
The negative sequence voltage is calculated from the three-phase voltage input within
the IED by using the pre-processing block. The preprocessing block will calculate the
negative sequence voltage from the three inputs into the pre-processing block by using
the following formula:
2
U =(UL1+alpha UL2 + alpha UL3)/3
×
×
GUID-87DA8E2C-B3E5-42D6-B909-59EA3F9309D8 V1 EN
(Equation 44)
where:
UL1, UL2 and UL3
are fundamental frequency phasors of three individual phase voltages.
alpha
unit phasor with an angle of 120 degrees.
The polarizing phasor is used together with the phasor of the operating directional
current, in order to determine the direction to the earth fault (Forward/Reverse). In
order to enable voltage polarizing the magnitude of polarizing voltage shall be bigger
than a minimum level defined by setting parameter
UpolMin
.
It shall be noted that residual voltage (U
n
) or negative sequence voltage (U
2
) is used
to determine the location of the earth fault. This insures the required inversion of the
polarizing voltage within the earth-fault function.
Section 8
1MRK 504 135-UEN A
Current protection
162
Technical manual
Содержание ret650
Страница 1: ...Relion 650 series Transformer protection RET650 Technical manual ...
Страница 2: ......
Страница 40: ...34 ...
Страница 62: ...56 ...
Страница 84: ...78 ...
Страница 208: ...202 ...
Страница 353: ...Table 236 Gray code conversion IEC06000523 V1 EN 1MRK 504 135 UEN A Section 12 Control 347 Technical manual ...
Страница 376: ...370 ...
Страница 414: ...408 ...
Страница 530: ...524 ...
Страница 562: ...556 ...
Страница 620: ...614 ...
Страница 668: ...662 ...
Страница 669: ...663 ...