corresponding information is available on the non-calculated output (AI4) on the
SMAI function block. Connect the signals to the AxRADR accordingly.
For each of the analog signals,
Operation
=
On
means that it is recorded by the
disturbance recorder. The trigger is independent of the setting of
Operation
, and
triggers even if operation is set to
Off
. Both undervoltage and overvoltage can be used
as trigger conditions. The same applies for the current signals.
If
Operation
=
Off
, no waveform (samples) will be recorded and reported in graph.
However, Trip value, pre-fault and fault value will be recorded and reported. The
input channel can still be used to trig the disturbance recorder.
If
Operation
=
On
, waveform (samples) will also be recorded and reported in graph.
The analog signals are presented only in the disturbance recording, but they affect the
entire disturbance report when being used as triggers.
14.4.6.10
Binary signals
Up to 96 binary signals can be selected to be handled by disturbance report. The
signals can be selected from internal logical and binary input signals. A binary signal
is selected to be recorded when:
•
the corresponding function block is included in the configuration
•
the signal is connected to the input of the function block
Each of the 96 signals can be selected as a trigger of the disturbance report (
Operation
=
Off
). A binary signal can be selected to activate the yellow (START) and red (TRIP)
LED on the local HMI (
SetLED
=
Off/Start/Trip/Start and Trip
).
The selected signals are presented in the event recorder, event list and the disturbance
recording. But they affect the whole disturbance report when they are used as triggers.
The indications are also selected from these 96 signals with local HMI
IndicationMask=Show/Hide
.
14.4.6.11
Trigger signals
The trigger conditions affect the entire disturbance report, except the event list, which
runs continuously. As soon as at least one trigger condition is fulfilled, a complete
disturbance report is recorded. On the other hand, if no trigger condition is fulfilled,
there is no disturbance report, no indications, and so on. This implies the importance
of choosing the right signals as trigger conditions.
A trigger can be of type:
•
Manual trigger
•
Binary-signal trigger
•
Analog-signal trigger (over/under function)
1MRK 504 135-UEN A
Section 14
Monitoring
471
Technical manual
Содержание ret650
Страница 1: ...Relion 650 series Transformer protection RET650 Technical manual ...
Страница 2: ......
Страница 40: ...34 ...
Страница 62: ...56 ...
Страница 84: ...78 ...
Страница 208: ...202 ...
Страница 353: ...Table 236 Gray code conversion IEC06000523 V1 EN 1MRK 504 135 UEN A Section 12 Control 347 Technical manual ...
Страница 376: ...370 ...
Страница 414: ...408 ...
Страница 530: ...524 ...
Страница 562: ...556 ...
Страница 620: ...614 ...
Страница 668: ...662 ...
Страница 669: ...663 ...