The BLOCK input will block only the signals in monitoring direction (the position
information), not the commands via IEC 60870-5-103. The SELECT input is used to
indicate that the monitored apparatus has been selected (in a select-before-operate
type of control)
12.13.2
Function block
IEC10000286-1-en.vsd
I103POSCMD
BLOCK
POSITION
SELECT
IEC10000286 V1 EN
Figure 162:
I103POSCMD function block
12.13.3
Signals
Table 272:
I103POSCMD Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block of command
POSITION
INTEGER
0
Position of controllable object
SELECT
BOOLEAN
0
Select of controllable object
12.13.4
Settings
Table 273:
I103POSCMD Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
FunctionType
1 - 255
-
1
1
Fucntion type (1-255)
InfNo
160 - 196
-
4
160
Information number for command output
(1-255)
1MRK 504 135-UEN A
Section 12
Control
369
Technical manual