13.9.2
Functionality
Elapsed Time Integrator (TEIGGIO) function is a function that accumulates the
elapsed time when a given binary signal has been high.
The main features of TEIGGIO are
•
Applicable to long time integration (≤999 999.9 seconds).
•
Supervision of limit transgression conditions and overflow.
•
Possibility defining a warning or alarm with the resolution of 10 milliseconds.
•
Retain the integration value at a warning/alarm/overflow.
•
Possibilities for blocking and reset.
•
Report the integrated time
13.9.3
Function block
TEIGGIO
BLOCK
IN
RESET
WARNING
ALARM
OVERFLOW
ACCTIME
IEC13000005-1-en.vsd
IEC13000005 V1 EN
Figure 183:
TEIGGIO function block
13.9.4
Signals
Table 323:
TEIGGIO Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Freeze the integration and block the other outputs
IN
BOOLEAN
0
The input signal that is used to measure the
elapsed time, when its value is high
RESET
BOOLEAN
0
Reset the integration time
Table 324:
TEIGGIO Output signals
Name
Type
Description
WARNING
BOOLEAN
Indicator of the integrated time has reached the
warning limit
ALARM
BOOLEAN
Indicator of the integrated time has reached the
alarm limit
OVERFLOW
BOOLEAN
Indicator of the integrated time has reached the
overflow limit
ACCTIME
REAL
Integrated elapsed time in seconds
Section 13
1MRK 504 135-UEN A
Logic
404
Technical manual
Содержание ret650
Страница 1: ...Relion 650 series Transformer protection RET650 Technical manual ...
Страница 2: ......
Страница 40: ...34 ...
Страница 62: ...56 ...
Страница 84: ...78 ...
Страница 208: ...202 ...
Страница 353: ...Table 236 Gray code conversion IEC06000523 V1 EN 1MRK 504 135 UEN A Section 12 Control 347 Technical manual ...
Страница 376: ...370 ...
Страница 414: ...408 ...
Страница 530: ...524 ...
Страница 562: ...556 ...
Страница 620: ...614 ...
Страница 668: ...662 ...
Страница 669: ...663 ...