Protected Object
Line, transformer, etc
Forward
Reverse
Definition of direction
for directional functions
Measured quantity is
positive when flowing
towards the object
e.g. P, Q, I
Reverse
Forward
Definition of direction
for directional functions
e.g. P, Q, I
Measured quantity is
positive when flowing
towards the object
Set parameter
CTStarPoint
Correct Setting is
"ToObject"
Set parameter
CTStarPoint
Correct Setting is
"FromObject"
en05000456.vsd
IEC05000456 V1 EN
Figure 2:
Internal convention of the directionality in the IED
If the settings of the primary CT is correct, that is
CTStarPoint
set as
FromObject
or
ToObject
according to the plant condition, then a positive quantity always flows
towards the protected object, and a
Forward
direction always looks towards the
protected object.
The settings of the IED is performed in primary values. The ratios of the main CTs and
VTs are therefore basic data for the IED. The user has to set the rated secondary and
primary currents and voltages of the CTs and VTs to provide the IED with their rated
ratios.
The CT and VT ratio and the name on respective channel is done under
Main menu/
Hardware/Analog modules
in the Parameter Settings tool or on the HMI.
3.3
Presumptions for technical data
The technical data stated in this document are only valid under the following
circumstances:
•
CT and VT ratios in the IED are set in accordance with the associated main
instrument transformers. Note that for functions which measure an analogue
signal which do not have corresponding primary quantity, the 1:1 ratio shall be set
for the used analogue inputs on the IED, For example, HZPDIF.
•
Parameter IBase used by the tested function is set equal to the rated CT primary
current.
•
Parameter UBase used by the tested function is set equal to the rated primary
phase-to-phase voltage.
•
Parameter SBase used by the tested function is set equal to sqrt(3)* IBase* UBase
for three-phase power system.
Section 3
1MRK 504 135-UEN A
Analog inputs
44
Technical manual
Содержание ret650
Страница 1: ...Relion 650 series Transformer protection RET650 Technical manual ...
Страница 2: ......
Страница 40: ...34 ...
Страница 62: ...56 ...
Страница 84: ...78 ...
Страница 208: ...202 ...
Страница 353: ...Table 236 Gray code conversion IEC06000523 V1 EN 1MRK 504 135 UEN A Section 12 Control 347 Technical manual ...
Страница 376: ...370 ...
Страница 414: ...408 ...
Страница 530: ...524 ...
Страница 562: ...556 ...
Страница 620: ...614 ...
Страница 668: ...662 ...
Страница 669: ...663 ...