12.1.5.5
Settings
Table 189:
QCBAY Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
AllPSTOValid
Priority
No priority
-
-
Priority
Priority of originators
12.1.6
Local remote LOCREM
12.1.6.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Local remote
LOCREM
-
-
12.1.6.2
Functionality
The signals from the local HMI or from an external local/remote switch are applied via
the function blocks LOCREM and LOCREMCTRL to the Bay control QCBAY
function block. A parameter in function block LOCREM is set to choose if the switch
signals are coming from the local HMI or from an external hardware switch connected
via binary inputs.
12.1.6.3
Function block
LOCREM
CTRLOFF
LOCCTRL
REMCTRL
LHMICTRL
OFF
LOCAL
REMOTE
VALID
IEC09000076_1_en.vsd
IEC09000076 V1 EN
Figure 119:
LOCREM function block
12.1.6.4
Signals
Table 190:
LOCREM Input signals
Name
Type
Default
Description
CTRLOFF
BOOLEAN
0
Disable control
LOCCTRL
BOOLEAN
0
Local in control
REMCTRL
BOOLEAN
0
Remote in control
LHMICTRL
INTEGER
0
LHMI control
1MRK 504 135-UEN A
Section 12
Control
263
Technical manual
Содержание ret650
Страница 1: ...Relion 650 series Transformer protection RET650 Technical manual ...
Страница 2: ......
Страница 40: ...34 ...
Страница 62: ...56 ...
Страница 84: ...78 ...
Страница 208: ...202 ...
Страница 353: ...Table 236 Gray code conversion IEC06000523 V1 EN 1MRK 504 135 UEN A Section 12 Control 347 Technical manual ...
Страница 376: ...370 ...
Страница 414: ...408 ...
Страница 530: ...524 ...
Страница 562: ...556 ...
Страница 620: ...614 ...
Страница 668: ...662 ...
Страница 669: ...663 ...