14.4.7
Technical data
Table 380:
DRPRDRE technical data
Function
Range or value
Accuracy
Current recording
-
± 1,0% of I
r
at I ≤ I
r
± 1,0% of I at I > Ir
Voltage recording
-
± 1,0% of U
r
at U ≤ U
r
± 1,0% of U at U > U
r
Pre-fault time
(0.05–3.00) s
-
Post-fault time
(0.1–10.0) s
-
Limit time
(0.5–8.0) s
-
Maximum number of recordings
100, first in - first out
-
Time tagging resolution
1 ms
See time synchronization
technical data
Maximum number of analog inputs
30 + 10 (ex internally
derived)
-
Maximum number of binary inputs
96
-
Maximum number of phasors in the
Trip Value recorder per recording
30
-
Maximum number of indications in a
disturbance report
96
-
Maximum number of events in the
Event recording per recording
150
-
Maximum number of events in the
Event list
1000, first in - first out
-
Maximum total recording time (3.4 s
recording time and maximum number
of channels, typical value)
340 seconds (100 recordings) at
50 Hz, 280 seconds (80
recordings) at 60 Hz
-
Sampling rate
1 kHz at 50 Hz
1.2 kHz at 60 Hz
-
Recording bandwidth
(5-300) Hz
-
14.5
Indications
14.5.1
Functionality
To get fast, condensed and reliable information about disturbances in the primary and/
or in the secondary system it is important to know, for example binary signals that
have changed status during a disturbance. This information is used in the short
perspective to get information via the local HMI in a straightforward way.
There are three LEDs on the local HMI (green, yellow and red), which will display
status information about the IED and the Disturbance recorder function (triggered).
The Indication list function shows all selected binary input signals connected to the
Disturbance recorder function that have changed status during a disturbance.
1MRK 504 135-UEN A
Section 14
Monitoring
473
Technical manual
Содержание ret650
Страница 1: ...Relion 650 series Transformer protection RET650 Technical manual ...
Страница 2: ......
Страница 40: ...34 ...
Страница 62: ...56 ...
Страница 84: ...78 ...
Страница 208: ...202 ...
Страница 353: ...Table 236 Gray code conversion IEC06000523 V1 EN 1MRK 504 135 UEN A Section 12 Control 347 Technical manual ...
Страница 376: ...370 ...
Страница 414: ...408 ...
Страница 530: ...524 ...
Страница 562: ...556 ...
Страница 620: ...614 ...
Страница 668: ...662 ...
Страница 669: ...663 ...