14.12.2
Functionality
IEC61850 generic communication I/O functions (MVGGIO) function is used to send
the instantaneous value of an analog signal to other systems or equipment in the
substation. It can also be used inside the same IED, to attach a RANGE aspect to an
analog value and to permit measurement supervision on that value.
14.12.3
Function block
IEC09000239-2-en.vsd
MVGGIO
BLOCK
^IN
^VALUE
RANGE
14.12.4
Signals
Table 389:
MVGGIO Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block of function
IN
REAL
0
Analog input value
Table 390:
MVGGIO Output signals
Name
Type
Description
VALUE
REAL
Magnitude of deadband value
RANGE
INTEGER
Range
14.12.5
Settings
Table 391:
MVGGIO Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
BasePrefix
micro
milli
unit
kilo
Mega
Giga
Tera
-
-
unit
Base prefix (multiplication factor)
MV db
1 - 300
Type
1
10
Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
MV zeroDb
0 - 100000
m%
1
500
Zero point clamping in 0,001% of range
MV hhLim
-5000.00 - 5000.00
xBase
0.01
900.00
High High limit multiplied with the base
prefix (multiplication factor)
MV hLim
-5000.00 - 5000.00
xBase
0.01
800.00
High limit multiplied with the base prefix
(multiplication factor)
Table continues on next page
Section 14
1MRK 504 135-UEN A
Monitoring
486
Technical manual
Содержание ret650
Страница 1: ...Relion 650 series Transformer protection RET650 Technical manual ...
Страница 2: ......
Страница 40: ...34 ...
Страница 62: ...56 ...
Страница 84: ...78 ...
Страница 208: ...202 ...
Страница 353: ...Table 236 Gray code conversion IEC06000523 V1 EN 1MRK 504 135 UEN A Section 12 Control 347 Technical manual ...
Страница 376: ...370 ...
Страница 414: ...408 ...
Страница 530: ...524 ...
Страница 562: ...556 ...
Страница 620: ...614 ...
Страница 668: ...662 ...
Страница 669: ...663 ...