Name
Type
Description
START1
BOOLEAN
Start signal from stage 1
START2
BOOLEAN
Start signal from stage 2
P
REAL
Active Power
PPERCENT
REAL
Active power in % of calculated power base value
Q
REAL
Reactive power
QPERCENT
REAL
Reactive power in % of calculated power base
value
8.8.2.4
Settings
Table 112:
GOPPDOP Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
Off
Operation Off / On
OpMode1
Off
OverPower
-
-
OverPower
Operation mode 1
Power1
0.0 - 500.0
%
0.1
1.0
Power setting for stage 1 in % of
calculated power base value
Angle1
-180.0 - 180.0
Deg
0.1
0.0
Characteristic angle for stage 1
TripDelay1
0.010 - 6000.000
s
0.001
1.000
Trip delay for stage 1
OpMode2
Off
OverPower
-
-
OverPower
Operation mode 2
Power2
0.0 - 500.0
%
0.1
1.0
Power setting for stage 2 in % of
calculated power base value
Angle2
-180.0 - 180.0
Deg
0.1
0.0
Characteristic angle for stage 2
TripDelay2
0.010 - 6000.000
s
0.001
1.000
Trip delay for stage 2
Table 113:
GOPPDOP Group settings (advanced)
Name
Values (Range)
Unit
Step
Default
Description
k
0.00 - 0.99
-
0.01
0.00
Low pass filter coefficient for power
measurement, U and I
Table 114:
GOPPDOP Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
GlobalBaseSel
1 - 6
-
1
1
Selection of one of the Global Base Value
groups
Mode
L1, L2, L3
Arone
Pos Seq
L1L2
L2L3
L3L1
L1
L2
L3
-
-
Pos Seq
Mode of measurement for current and
voltage
1MRK 504 135-UEN A
Section 8
Current protection
191
Technical manual
Содержание ret650
Страница 1: ...Relion 650 series Transformer protection RET650 Technical manual ...
Страница 2: ......
Страница 40: ...34 ...
Страница 62: ...56 ...
Страница 84: ...78 ...
Страница 208: ...202 ...
Страница 353: ...Table 236 Gray code conversion IEC06000523 V1 EN 1MRK 504 135 UEN A Section 12 Control 347 Technical manual ...
Страница 376: ...370 ...
Страница 414: ...408 ...
Страница 530: ...524 ...
Страница 562: ...556 ...
Страница 620: ...614 ...
Страница 668: ...662 ...
Страница 669: ...663 ...