Table 233:
TCMYLTC Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
GlobalBaseSel
1 - 6
-
1
1
Selection of one of the Global Base Value
groups
LowVoltTap
1 - 63
-
1
1
Tap position for the lowest voltage
HighVoltTap
1 - 63
-
1
33
Tap position for the highest voltage
mALow
0.000 - 25.000
mA
0.001
4.000
mA for the lowest voltage tap position
mAHigh
0.000 - 25.000
mA
0.001
20.000
mA for the highest voltage tap position
CodeType
Binary
BCD
Gray
ContactPerTap
mA
-
-
Binary
Type of code conversion
UseParity
Off
On
-
-
Off
Enable parity check
tStable
1 - 60
s
1
2
Time after position change before the
value is accepted
CLFactor
1.0 - 3.0
-
0.1
2.0
Adjustable factor for contact life function
InitCLCounter
0 - 9999999
s
1
250000
CL counter start value
EnabTapCmd
Off
On
-
-
On
Enable commands to tap changer
12.3.3.5
Monitored data
Table 234:
TCMYLTC Monitored data
Name
Type
Values (Range)
Unit
Description
CNT_VAL
INTEGER
-
-
Number of operations on
tap changer
CLCNT_VAL
REAL
-
-
Remaining number of
operations at rated load
TCPOS
INTEGER
-
-
Integer value
corresponding to actual
tap position
12.3.4
Operation principle
The voltage control function is built up by two function blocks. Both are logical nodes
in IEC 61850-8-1.
•
Automatic voltage control for tap changer
•
TR8ATCC
•
Tap changer control and supervision
•
TCMYLTC, 6 binary inputs
1MRK 504 135-UEN A
Section 12
Control
341
Technical manual
Содержание ret650
Страница 1: ...Relion 650 series Transformer protection RET650 Technical manual ...
Страница 2: ......
Страница 40: ...34 ...
Страница 62: ...56 ...
Страница 84: ...78 ...
Страница 208: ...202 ...
Страница 353: ...Table 236 Gray code conversion IEC06000523 V1 EN 1MRK 504 135 UEN A Section 12 Control 347 Technical manual ...
Страница 376: ...370 ...
Страница 414: ...408 ...
Страница 530: ...524 ...
Страница 562: ...556 ...
Страница 620: ...614 ...
Страница 668: ...662 ...
Страница 669: ...663 ...