12.6
IEC 61850 generic communication I/O functions
DPGGIO
12.6.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
IEC 61850 generic communication I/O
functions
DPGGIO
-
-
12.6.2
Functionality
The IEC 61850 generic communication I/O functions DPGGIO function block is used
to send double indications to other systems or equipment in the substation using
IEC61850. It is especially used in the interlocking and reservation station-wide logics.
12.6.3
Function block
DPGGIO
OPEN
CLOSE
VALID
POSITION
IEC09000075_1_en.vsd
IEC09000075 V1 EN
Figure 155:
DPGGIO function block
12.6.4
Signals
Table 252:
DPGGIO Input signals
Name
Type
Default
Description
OPEN
BOOLEAN
0
Open indication
CLOSE
BOOLEAN
0
Close indication
VALID
BOOLEAN
0
Valid indication
Table 253:
DPGGIO Output signals
Name
Type
Description
POSITION
INTEGER
Double point indication
Section 12
1MRK 504 135-UEN A
Control
358
Technical manual
Содержание ret650
Страница 1: ...Relion 650 series Transformer protection RET650 Technical manual ...
Страница 2: ......
Страница 40: ...34 ...
Страница 62: ...56 ...
Страница 84: ...78 ...
Страница 208: ...202 ...
Страница 353: ...Table 236 Gray code conversion IEC06000523 V1 EN 1MRK 504 135 UEN A Section 12 Control 347 Technical manual ...
Страница 376: ...370 ...
Страница 414: ...408 ...
Страница 530: ...524 ...
Страница 562: ...556 ...
Страница 620: ...614 ...
Страница 668: ...662 ...
Страница 669: ...663 ...