comes to password, upon pressing the
key, the following characters will show up:
“
✳✳✳✳✳✳✳✳
”. The user must scroll for every letter in the password. After all the
letters are introduced (passwords are case sensitive) choose OK and press the
key
again.
At successful Log on, the local HMI shows the new user name in the status bar at the
bottom of the LCD. If the Log on is OK, when required to change for example a
password protected setting, the local HMI returns to the actual setting folder. If the
Log on has failed, an "Error Access Denied" message opens. If a user enters an
incorrect password three times, that user will be blocked for ten minutes before a new
attempt to log in can be performed. The user will be blocked from logging in, both
from the local HMI and PCM600. However, other users are to log in during this
period.
17.13
Authority management AUTHMAN
17.13.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Authority management
AUTHMAN
-
-
17.13.2
AUTHMAN
This function enables/disables the maintenance menu. It also controls the
maintenance menu log on time out.
17.13.3
Settings
Table 508:
AUTHMAN Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
MaintMenuEnable
No
Yes
-
-
Yes
Maintenance menu enabled
AuthTimeout
10 Min
20 Min
30 Min
40 Min
50 Min
60 Min
-
-
10 Min
Authority blocking timeout
Section 17
1MRK 504 135-UEN A
Basic IED functions
594
Technical manual
Содержание ret650
Страница 1: ...Relion 650 series Transformer protection RET650 Technical manual ...
Страница 2: ......
Страница 40: ...34 ...
Страница 62: ...56 ...
Страница 84: ...78 ...
Страница 208: ...202 ...
Страница 353: ...Table 236 Gray code conversion IEC06000523 V1 EN 1MRK 504 135 UEN A Section 12 Control 347 Technical manual ...
Страница 376: ...370 ...
Страница 414: ...408 ...
Страница 530: ...524 ...
Страница 562: ...556 ...
Страница 620: ...614 ...
Страница 668: ...662 ...
Страница 669: ...663 ...