12.4.6
Monitored data
Table 248:
SLGGIO Monitored data
Name
Type
Values (Range)
Unit
Description
SWPOSN
INTEGER
-
-
Switch position as integer
value
12.4.7
Operation principle
The logic rotating switch for function selection and LHMI presentation (SLGGIO)
function has two operating inputs – UP and DOWN. When a signal is received on the
UP input, the block will activate the output next to the present activated output, in
ascending order (if the present activated output is 3 – for example and one operates the
UP input, then the output 4 will be activated). When a signal is received on the DOWN
input, the block will activate the output next to the present activated output, in
descending order (if the present activated output is 3 – for example and one operates
the DOWN input, then the output 2 will be activated). Depending on the output
settings the output signals can be steady or pulsed. In case of steady signals, in case of
UP or DOWN operation, the previously active output will be deactivated. Also,
depending on the settings one can have a time delay between the UP or DOWN
activation signal positive front and the output activation.
Besides the inputs visible in the application configuration in the Application
Configuration tool, there are other possibilities that will allow an user to set the desired
position directly (without activating the intermediate positions), either locally or
remotely, using a “select before execute” dialog. One can block the function
operation, by activating the BLOCK input. In this case, the present position will be
kept and further operation will be blocked. The operator place (local or remote) is
specified through the PSTO input. If any operation is allowed the signal INTONE
from the Fixed signal function block can be connected. SLGGIO function block has
also an integer value output, that generates the actual position number. The positions
and the block names are fully settable by the user. These names will appear in the
menu, so the user can see the position names instead of a number.
12.5
Selector mini switch VSGGIO
12.5.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Selector mini switch
VSGGIO
-
-
1MRK 504 135-UEN A
Section 12
Control
355
Technical manual
Содержание ret650
Страница 1: ...Relion 650 series Transformer protection RET650 Technical manual ...
Страница 2: ......
Страница 40: ...34 ...
Страница 62: ...56 ...
Страница 84: ...78 ...
Страница 208: ...202 ...
Страница 353: ...Table 236 Gray code conversion IEC06000523 V1 EN 1MRK 504 135 UEN A Section 12 Control 347 Technical manual ...
Страница 376: ...370 ...
Страница 414: ...408 ...
Страница 530: ...524 ...
Страница 562: ...556 ...
Страница 620: ...614 ...
Страница 668: ...662 ...
Страница 669: ...663 ...