Name
Type
Description
BC12OPTR
BOOLEAN
No connection via the own bus coupler between
WA1 and WA2
BC12CLTR
BOOLEAN
Connection exists via the own bus coupler between
WA1 and WA2
BC17OPTR
BOOLEAN
No connection via the own bus coupler between
WA1 and WA7
BC17CLTR
BOOLEAN
Connection exists via the own bus coupler between
WA1 and WA7
BC27OPTR
BOOLEAN
No connection via the own bus coupler between
WA2 and WA7
BC27CLTR
BOOLEAN
Connection exists via the own bus coupler between
WA2 and WA7
VPQB1TR
BOOLEAN
Switch status of QB1 is valid (open or closed)
VQB220TR
BOOLEAN
Switch status of QB2 and QB20 are valid (open or
closed)
VPQB7TR
BOOLEAN
Switch status of QB7 is valid (open or closed)
VPQB12TR
BOOLEAN
Switch status of QB1 and QB2 are valid (open or
closed)
VPBC12TR
BOOLEAN
Status of the bus coupler apparatuses between
WA1 and WA2 are valid
VPBC17TR
BOOLEAN
Status of the bus coupler apparatuses between
WA1 and WA7 are valid
VPBC27TR
BOOLEAN
Status of the bus coupler apparatuses between
WA2 and WA7 are valid
12.2.4.6
Settings
The function does not have any settings available in Local HMI or Protection and
Control IED Manager (PCM600).
12.2.5
Interlocking for 1 1/2 CB BH
12.2.5.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Interlocking for 1 1/2 breaker diameter
BH_CONN
-
3
Interlocking for 1 1/2 breaker diameter
BH_LINE_A
-
3
Interlocking for 1 1/2 breaker diameter
BH_LINE_B
-
3
1MRK 504 135-UEN A
Section 12
Control
289
Technical manual
Содержание ret650
Страница 1: ...Relion 650 series Transformer protection RET650 Technical manual ...
Страница 2: ......
Страница 40: ...34 ...
Страница 62: ...56 ...
Страница 84: ...78 ...
Страница 208: ...202 ...
Страница 353: ...Table 236 Gray code conversion IEC06000523 V1 EN 1MRK 504 135 UEN A Section 12 Control 347 Technical manual ...
Страница 376: ...370 ...
Страница 414: ...408 ...
Страница 530: ...524 ...
Страница 562: ...556 ...
Страница 620: ...614 ...
Страница 668: ...662 ...
Страница 669: ...663 ...