14.21.4
Settings
Table 422:
I103EF Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
FunctionType
1 - 255
-
1
160
Function type (1-255)
14.22
Function status fault protection for IEC 60870-5-103
I103FLTPROT
14.22.1
Functionality
I103FLTPROT is used for fault indications in monitor direction. Each input on the
function block is specific for a certain fault type and therefore must be connected to a
correspondent signal present in the configuration. For example: 68_TRGEN
represents the General Trip of the device, and therefore must be connected to the
general trip signal SMPPTRC_TRIP or equivalent.
The delay observed in the protocol is the time difference in between the signal that is
triggering the Disturbance Recorder and the respective configured signal to the IEC
60870-5-103 I103FLTPROT.
1MRK 504 135-UEN A
Section 14
Monitoring
517
Technical manual