Section 10
1MAC309294-MB F
General function block features
546
RER620
Technical Manual
Consequently, the measurement mode can be selected according to the application.
In extreme cases, for example with high overcurrent or harmonic content, the
measurement modes function in a slightly different way. The operation accuracy is defined
with the frequency range of f/fn=0.95...1.05. In peak-to-peak and RMS measurement
modes, the harmonics of the phase currents are not suppressed, whereas in the fundamental
frequency measurement the suppression of harmonics is at least -50 dB at the frequency
range of f= n x fn, where n = 2, 3, 4, 5,...
RMS
The RMS measurement principle is selected with the
Measurement mode
setting using the
value “RMS”. RMS consists of both AC and DC components. The AC component is the
effective mean value of the positive and negative peak values. RMS is used in applications
where the effect of the DC component must be taken into account.
RMS is calculated according to the formula:
(Equation 68)
n
the number of samples in a calculation cycle
I
i
the current sample value
DFT
The DFT measurement principle is selected with the
Measurement mode
setting using the
value “DFT”. In the DFT mode, the fundamental frequency component of the measured
signal is numerically calculated from the samples. In some applications, for example, it
can be difficult to accomplish sufficiently sensitive settings and accurate operation of the
low stage, which may be due to a considerable amount of harmonics on the primary side
currents. In such a case, the operation can be based solely on the fundamental frequency
component of the current. In addition, the DFT mode has slightly higher CT requirements
than the peak-to-peak mode, if used with high and instantaneous stages.
Peak-to-peak
The peak-to-peak measurement principle is selected with the
Measurement mode
setting
using the value “Peak-to-Peak”. It is the fastest measurement mode, in which the
measurement quantity is made by calculating the average from the positive and negative
peak values. The DC component is not included. The retardation time is short. The
damping of the harmonics is quite low and practically determined by the characteristics of
the anti-aliasing filter of the relay inputs. Consequently, this mode is usually used in
conjunction with high and instantaneous stages, where the suppression of harmonics is not
so important. In addition, the peak-to-peak mode allows considerable CT saturation
without impairing the performance of the operation.
I
RMS
i
i
n
n
I
=
=
∑
1
2
1
Содержание RER620
Страница 1: ...Relion Protection and Control Advanced Recloser Protection and Control RER620 Technical Manual ...
Страница 2: ......
Страница 22: ...Section 1MAC309294 MB F 16 RER620 Technical Manual ...
Страница 88: ...Section 3 1MAC309294 MB F Basic functions 82 RER620 Technical Manual ...
Страница 278: ...Section 4 1MAC309294 MB F Protection functions 272 RER620 Technical Manual ...
Страница 362: ...Section 5 1MAC309294 MB F Control functions 356 RER620 Technical Manual ...
Страница 418: ...Section 7 1MAC309294 MB F Measurement functions 412 RER620 Technical Manual ...
Страница 428: ...Section 8 1MAC309294 MB F Recording functions 422 RER620 Technical Manual ...
Страница 464: ...Section 9 1MAC309294 MB F Other functions 458 RER620 Technical Manual ...
Страница 554: ...Section 10 1MAC309294 MB F General function block features 548 RER620 Technical Manual ...
Страница 568: ...Section 12 1MAC309294 MB F Relay physical connections 562 RER620 Technical Manual ...
Страница 574: ...Section 13 1MAC309294 MB F Technical data 568 RER620 Technical Manual ...
Страница 576: ...Section 14 1MAC309294 MB F Relay and functionality tests 570 RER620 Technical Manual ...
Страница 578: ...Section 15 1MAC309294 MB F Applicable standards and regulations 572 RER620 Technical Manual ...
Страница 582: ...Section 16 1MAC309294 MB F Glossary 576 RER620 Technical Manual ...
Страница 583: ......