1MAC309294-MB F
Section 5
Control functions
RER620
349
Technical Manual
recloser B operation, and if the voltage does not return for the livebus timer setting, will
request the RER620 to start its SWOTF timer and, if programmed, to use New Group
Settings after t2 seconds (typically set around 10 seconds after the Sectionalizer is set to
trip). See Figure 187 the tie-point recloser T at the same instant will recognize a loss of
3-phase voltage on the S1 side of its recloser PTs. After a delay time of t3 seconds from
the initial fault at S1 the tie-point recloser T will close, and if programmed, switch to New
Group Settings. Since the fault is permanent, fault current will flow from the alternate
source. With proper coordination in this direction, the mid-point recloser will trip on
overcurrent (one shot due to its SWOTF mode), isolating the faulted section between
Recloser B and C. This establishes service from S2 to Recloser C. The TiePoint recloser
is typically set to declare its phase voltages dead sometime after the Midpoint recloser has
started its SWOTF timer and before the SWOTF timer expires. The unfaulted portion of
the distribution feeder circuit from S2 to recloser B never loses service, and from Recloser
C to the tie-point recloser the load is picked back up. Figure 187 and
Table 316 summarize
the events.
Figure 187:
5-Reclosre Fault 2 scenario Sequence of Events
Table 316: 5-Reclosre Fault 2 scenario Sequence of Events
5-Recloser Fault 3 Scenario
If a permanent fault occurred at location F3, Figure 186, the following sequence occurs;
recloser C proceeds through its reclosing sequence of overcurrent protection (assume 3
operations to lockout). Upon tripping of recloser C, recloser T senses loss of voltage and
after its time delay of t1 seconds, closes onto the permanent fault. Since this fault is
permanent and recloser T has closed into the fault, recloser T does not go through the same
recloser sequence as recloser C just went through, recloser T goes directly to lockout. The
unfaulted portion of the distribution feeder circuit between S1 to recloser C remains in
Time
Event or Conditon
t0
Permanent line fault occurs. Sectionalizing recloser trips and locks out causing loss of
voltage at the Midpoint and TiePoint reclosers.
t1
Midpoint recloser declares phases dead, initiates loop control sequence, starts SWOTF
timer. May request ALT thresholds (per settings).
t2
TiePoint recloser declares phases dead, initiates loop control sequence and closes its
breaker. May request ALT thresholds (per settings) before closing breaker.
Recloser B
Permanent
Fault Initiates
Recloser C senses loss
of voltage and chages
to ALT1 setting
Recloser T
changes to ALT1
setting and closes
t1 + 5s
2
t
0
t
t1
45 s - 3rd reclose and lockout
15 s - 2nd reclose
0.5 s - 1st reclose
Содержание RER620
Страница 1: ...Relion Protection and Control Advanced Recloser Protection and Control RER620 Technical Manual ...
Страница 2: ......
Страница 22: ...Section 1MAC309294 MB F 16 RER620 Technical Manual ...
Страница 88: ...Section 3 1MAC309294 MB F Basic functions 82 RER620 Technical Manual ...
Страница 278: ...Section 4 1MAC309294 MB F Protection functions 272 RER620 Technical Manual ...
Страница 362: ...Section 5 1MAC309294 MB F Control functions 356 RER620 Technical Manual ...
Страница 418: ...Section 7 1MAC309294 MB F Measurement functions 412 RER620 Technical Manual ...
Страница 428: ...Section 8 1MAC309294 MB F Recording functions 422 RER620 Technical Manual ...
Страница 464: ...Section 9 1MAC309294 MB F Other functions 458 RER620 Technical Manual ...
Страница 554: ...Section 10 1MAC309294 MB F General function block features 548 RER620 Technical Manual ...
Страница 568: ...Section 12 1MAC309294 MB F Relay physical connections 562 RER620 Technical Manual ...
Страница 574: ...Section 13 1MAC309294 MB F Technical data 568 RER620 Technical Manual ...
Страница 576: ...Section 14 1MAC309294 MB F Relay and functionality tests 570 RER620 Technical Manual ...
Страница 578: ...Section 15 1MAC309294 MB F Applicable standards and regulations 572 RER620 Technical Manual ...
Страница 582: ...Section 16 1MAC309294 MB F Glossary 576 RER620 Technical Manual ...
Страница 583: ......