1MAC309294-MB F
Section 4
Protection functions
RER620
219
Technical Manual
Table 234: Operation modes for operation logic
Operation mode
Description
Freq<
The function operates independently as the underfrequency (“Freq<“) protection
function. When the measured frequency is below the set value of the
Start value Freq<
setting, the module activates the
START
and
STR_UFRQ
outputs. The time
characteristic is according to DT. When the operation timer has reached the value set
by the
Operate Tm Freq
setting, the
OPERATE
and
OPR_UFRQ
outputs are activated. If
the frequency restores before the module operates, the reset timer is activated. If the
timer reaches the value set by the
Reset delay Tm Freq
setting, the operate timer
resets and the
START
and
STR_UFRQ
outputs are deactivated.
Freq>
The function operates independently as the overfrequency (“Freq>”) protection
function. When the measured frequency exceeds the set value of the
Start value Freq>
setting, the module activates the
START
and
STR_OFRQ
outputs. The time
characteristic is according to DT. When the operation timer has reached the value set
by the
Operate Tm Freq
setting, the
OPERATE
and
OPR_OFRQ
outputs are activated. If
the frequency restores before the module operates, the reset timer is activated. If the
timer reaches the value set by the
Reset delay Tm Freq
setting, the operate timer
resets and the
START
and
STR_OFRQ
outputs are deactivated.
df/dt
The function operates independently as the frequency gradient (“df/dt”), rate-of-change,
protection function. When the frequency gradient exceeds the set value of the
Start
value df/dt
setting, the module activates the
START
and
STR_FRG
outputs. The time
characteristic is according to DT. When the operation timer has reached the value set
by the
Operate Tm df/dt
setting, the
OPERATE
and
OPR_FRG
outputs are activated. If
the frequency gradient restores before the module operates, the reset timer is
activated. If the timer reaches the value set by the
Reset delay Tm df/dt
setting, the
operate timer resets and the
START
and
STR_FRG
outputs are deactivated.
Freq< + df/dt
A consecutive operation is enabled between the protection methods. When the
measured frequency is below the set value of the
Start value Freq<
setting, the
frequency gradient protection is enabled. After the frequency has dropped below the
set value, the frequency gradient is compared to the set value of the
Start value df/dt
setting. When the frequency gradient exceeds the set value, the module activates the
START
and
STR_FRG
outputs. The time characteristic is according to DT. When the
operation timer has reached the value set by the
Operate Tm df/dt
setting, the
OPERATE
and
OPR_FRG
outputs are activated. If the frequency gradient restores before
the module operates, the reset timer is activated. If the timer reaches the value set by
the
Reset delay Tm df/dt
setting, the operate timer resets and the
START
and
STR_FRG
outputs are deactivated. The
OPR_UFRQ
output is not active when this operation mode
is used.
Freq> + df/dt
A consecutive operation is enabled between the protection methods. When the
measured frequency exceeds the set value of the
Start value Freq>
setting, the
frequency gradient protection is enabled. After the frequency exceeds the set value, the
frequency gradient is compared to the set value of the
Start value df/dt
setting. When
the frequency gradient exceeds the set value, the module activates the
START
and
STR_FRG
outputs. The time characteristic is according to DT. When the operation timer
has reached the value set by the
Operate Tm df/dt
setting, the
OPERATE
and
OPR_FRG
outputs are activated. If the frequency gradient restores before the module operates,
the reset timer is activated. If the timer reaches the value set by the
Reset delay Tm
df/dt
setting, the operate timer resets and the
START
and
STR_FRG
outputs are
deactivated. The
OPR_OFRQ
output is not active when this operation mode is used.
Freq< OR df/dt
A parallel operation between the protection methods is enabled. The
START
output is
activated when either of the measured values of the protection module exceeds its set
value. Detailed information about the active module is available at the
STR_UFRQ
and
STR_FRG
outputs. The shortest operate delay time from the set
Operate Tm Freq
or
Operate Tm df/dt
is dominant regarding the
OPERATE
output. The time characteristic is
according to DT. The characteristic that activates the
OPERATE
output can be seen
from the
OPR_UFRQ
or
OPR_FRG
output. If the frequency gradient restores before the
module operates, the reset timer is activated. If the timer reaches the value set by the
Reset delay Tm df/dt
setting, the operate timer resets and the
STR_FRG
output is
deactivated. If the frequency restores before the module operates, the reset timer is
activated. If the timer reaches the value set by the
Reset delay Tm Freq
setting, the
operate timer resets and the
STR_UFRQ
output is deactivated.
Содержание RER620
Страница 1: ...Relion Protection and Control Advanced Recloser Protection and Control RER620 Technical Manual ...
Страница 2: ......
Страница 22: ...Section 1MAC309294 MB F 16 RER620 Technical Manual ...
Страница 88: ...Section 3 1MAC309294 MB F Basic functions 82 RER620 Technical Manual ...
Страница 278: ...Section 4 1MAC309294 MB F Protection functions 272 RER620 Technical Manual ...
Страница 362: ...Section 5 1MAC309294 MB F Control functions 356 RER620 Technical Manual ...
Страница 418: ...Section 7 1MAC309294 MB F Measurement functions 412 RER620 Technical Manual ...
Страница 428: ...Section 8 1MAC309294 MB F Recording functions 422 RER620 Technical Manual ...
Страница 464: ...Section 9 1MAC309294 MB F Other functions 458 RER620 Technical Manual ...
Страница 554: ...Section 10 1MAC309294 MB F General function block features 548 RER620 Technical Manual ...
Страница 568: ...Section 12 1MAC309294 MB F Relay physical connections 562 RER620 Technical Manual ...
Страница 574: ...Section 13 1MAC309294 MB F Technical data 568 RER620 Technical Manual ...
Страница 576: ...Section 14 1MAC309294 MB F Relay and functionality tests 570 RER620 Technical Manual ...
Страница 578: ...Section 15 1MAC309294 MB F Applicable standards and regulations 572 RER620 Technical Manual ...
Страница 582: ...Section 16 1MAC309294 MB F Glossary 576 RER620 Technical Manual ...
Страница 583: ......