Section 4
1MAC309294-MB F
Protection functions
178
RER620
Technical Manual
Table 186: 46 Non group settings
4.1.6.8
Monitored data
Table 187: 46 Monitored data
4.1.6.9
Technical data
Table 188: 46 Technical data
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=Enable
5=Disable
5=Disable
Operation Disable / Enable
Minimum trip time
20...60000
ms
1
20
Minimum trip time for IDMT curves
Reset delay time
0...60000
ms
1
20
Reset delay time
Curve parameter A
0.0086...120.0000
28.2000
Parameter A for customer programmable curve
Curve parameter B
0.0000...0.7120
0.1217
Parameter B for customer programmable curve
Curve parameter C
0.02...2.00
2.00
Parameter C for customer programmable curve
Curve parameter D
0.46...30.00
29.10
Parameter D for customer programmable curve
Curve parameter E
0.0...1.0
1.0
Parameter E for customer programmable curve
Name
Type
Values (Range)
Unit
Description
PICKUP_DUR
FLOAT32
0.00...100.00
%
Ratio of pickup time / trip
time
46
Enum
1=enabled
2=blocked
3=test
4=test/blocked
5=disabled
Status
Operation accuracy
Depending on the frequency of the current
measured: f
n
±2Hz
±1.5% of the set value or ±0.002 x I
n
Pickup time
1 ,2
1. Negative sequence current before fault = 0.0, f
n
= 60 Hz, results based on statistical distribution of 1000
measurements
2. Includes the delay of the signal output contact
Minimum
Typical
Maximum
I
Fault
= 2 x set
Pickup value
I
Fault
= 10 x set
Pickup value
22 ms
14 ms
24 ms
16 ms
25 ms
17 ms
Reset time
< 40 ms
Reset ratio
Typical 0.96
Retardation time
< 35 ms
Trip time accuracy in definite time mode
±1.0% of the set value or ±20 ms
Trip time accuracy in inverse time mode
±5.0% of the theoretical value or ±20 ms
3
3. Maximum
Pickup value
= 2.5 x I
n
,
Pickup value
multiples in range of 1.5 to 20
Suppression of harmonics
DFT: -50dB at f = n x f
n
, where n = 2, 3, 4, 5,…
Содержание RER620
Страница 1: ...Relion Protection and Control Advanced Recloser Protection and Control RER620 Technical Manual ...
Страница 2: ......
Страница 22: ...Section 1MAC309294 MB F 16 RER620 Technical Manual ...
Страница 88: ...Section 3 1MAC309294 MB F Basic functions 82 RER620 Technical Manual ...
Страница 278: ...Section 4 1MAC309294 MB F Protection functions 272 RER620 Technical Manual ...
Страница 362: ...Section 5 1MAC309294 MB F Control functions 356 RER620 Technical Manual ...
Страница 418: ...Section 7 1MAC309294 MB F Measurement functions 412 RER620 Technical Manual ...
Страница 428: ...Section 8 1MAC309294 MB F Recording functions 422 RER620 Technical Manual ...
Страница 464: ...Section 9 1MAC309294 MB F Other functions 458 RER620 Technical Manual ...
Страница 554: ...Section 10 1MAC309294 MB F General function block features 548 RER620 Technical Manual ...
Страница 568: ...Section 12 1MAC309294 MB F Relay physical connections 562 RER620 Technical Manual ...
Страница 574: ...Section 13 1MAC309294 MB F Technical data 568 RER620 Technical Manual ...
Страница 576: ...Section 14 1MAC309294 MB F Relay and functionality tests 570 RER620 Technical Manual ...
Страница 578: ...Section 15 1MAC309294 MB F Applicable standards and regulations 572 RER620 Technical Manual ...
Страница 582: ...Section 16 1MAC309294 MB F Glossary 576 RER620 Technical Manual ...
Страница 583: ......