Section 4
1MAC309294-MB F
Protection functions
172
RER620
Technical Manual
4.1.6
Negative phase-sequence current protection 46
4.1.6.1
Identification
4.1.6.2
Function block
Figure 76:
Function block
4.1.6.3
Functionality
The negative sequence current protection 46 is used for increasing sensitivity to detect
single phasing situations, unbalanced loads due to, for example, unsymmetrical feeder
voltages.
The function is based on the measurement of the negative sequence current. In a fault
situation, the function picks up when the negative sequence current exceeds the set limit.
The trip time characteristics can be selected to be either definite time (DT) or inverse
definite minimum time (IDMT). In the DT mode, the function trips after a predefined trip
time and resets when the fault current disappears. The IDMT mode provides current
dependent timer characteristics.
The function contains a blocking functionality. It is possible to block function outputs,
timers, or the function itself, if desired.
4.1.6.4
Operation principle
The function can be enabled and disabled with the
Operation
setting. The corresponding
parameter values are Enable and Disable.
The operation of negative phase-sequence current protection can be described by using a
module diagram. All the blocks in the diagram are explained in the next sections.
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Negative sequence current protection
NSPTOC
I2>
46
46 can also be used for detecting broken conductors.
Содержание RER620
Страница 1: ...Relion Protection and Control Advanced Recloser Protection and Control RER620 Technical Manual ...
Страница 2: ......
Страница 22: ...Section 1MAC309294 MB F 16 RER620 Technical Manual ...
Страница 88: ...Section 3 1MAC309294 MB F Basic functions 82 RER620 Technical Manual ...
Страница 278: ...Section 4 1MAC309294 MB F Protection functions 272 RER620 Technical Manual ...
Страница 362: ...Section 5 1MAC309294 MB F Control functions 356 RER620 Technical Manual ...
Страница 418: ...Section 7 1MAC309294 MB F Measurement functions 412 RER620 Technical Manual ...
Страница 428: ...Section 8 1MAC309294 MB F Recording functions 422 RER620 Technical Manual ...
Страница 464: ...Section 9 1MAC309294 MB F Other functions 458 RER620 Technical Manual ...
Страница 554: ...Section 10 1MAC309294 MB F General function block features 548 RER620 Technical Manual ...
Страница 568: ...Section 12 1MAC309294 MB F Relay physical connections 562 RER620 Technical Manual ...
Страница 574: ...Section 13 1MAC309294 MB F Technical data 568 RER620 Technical Manual ...
Страница 576: ...Section 14 1MAC309294 MB F Relay and functionality tests 570 RER620 Technical Manual ...
Страница 578: ...Section 15 1MAC309294 MB F Applicable standards and regulations 572 RER620 Technical Manual ...
Страница 582: ...Section 16 1MAC309294 MB F Glossary 576 RER620 Technical Manual ...
Страница 583: ......