Section 4
1MAC309294-MB F
Protection functions
148
RER620
Technical Manual
coil or the grounding resistor. This is the case for instance, when a directional ground-fault
relay is used in an MV-switching substation some kilometers from the HV/MV -substation
in which the grounding facilities are located. Another example is when
HV/MV-substations are connected in parallel but located far from each other.
It is easy to give the tripping sector such a width that all possible directions of the
I
0
-phasors of a faulty line are covered by one and the same sector. Thus, the problem of
setting the characteristic angle according to the grounding status of the network is easily
solved. There is no need to change any settings when a Petersen coil or a grounding resistor
is switched on or off. Auxiliary switches and other pieces of extra hardware are no longer
required for ensuring the selectivity of the directional ground-fault protection.
Figure 64:
Extended operation area in directional ground-fault protection
4.1.4.6
Measurement modes
The function operates on three alternative measurement modes: “RMS”, “DFT” and
“Peak-to-Peak”. The measurement mode is selected with the
Measurement mode
setting.
Table 166: Measurement modes supported by 67/51N and 67/50N stages
Max forward angle
RCA=0°
Current start value
Positive
operation
sector
Negative
operation
sector
-
Min forward angle
0
V
0
I
Measurement mode
Supported measurement modes
67/51N and 67/50N-1
67/50N-2
RMS
x
x
DFT
x
x
Peak-to-Peak
x
x
For a detailed description of the measurement modes, see the General
function block features section in this manual.
Содержание RER620
Страница 1: ...Relion Protection and Control Advanced Recloser Protection and Control RER620 Technical Manual ...
Страница 2: ......
Страница 22: ...Section 1MAC309294 MB F 16 RER620 Technical Manual ...
Страница 88: ...Section 3 1MAC309294 MB F Basic functions 82 RER620 Technical Manual ...
Страница 278: ...Section 4 1MAC309294 MB F Protection functions 272 RER620 Technical Manual ...
Страница 362: ...Section 5 1MAC309294 MB F Control functions 356 RER620 Technical Manual ...
Страница 418: ...Section 7 1MAC309294 MB F Measurement functions 412 RER620 Technical Manual ...
Страница 428: ...Section 8 1MAC309294 MB F Recording functions 422 RER620 Technical Manual ...
Страница 464: ...Section 9 1MAC309294 MB F Other functions 458 RER620 Technical Manual ...
Страница 554: ...Section 10 1MAC309294 MB F General function block features 548 RER620 Technical Manual ...
Страница 568: ...Section 12 1MAC309294 MB F Relay physical connections 562 RER620 Technical Manual ...
Страница 574: ...Section 13 1MAC309294 MB F Technical data 568 RER620 Technical Manual ...
Страница 576: ...Section 14 1MAC309294 MB F Relay and functionality tests 570 RER620 Technical Manual ...
Страница 578: ...Section 15 1MAC309294 MB F Applicable standards and regulations 572 RER620 Technical Manual ...
Страница 582: ...Section 16 1MAC309294 MB F Glossary 576 RER620 Technical Manual ...
Страница 583: ......