Section 5
1MAC309294-MB F
Control functions
332
RER620
Technical Manual
Network and the generator running in parallel with the network are connected through the
line AB. When a fault occurs between A and B, the relay protection opens the circuit
breakers A and B, thus isolating the faulty section from the network and making the arc
that caused the fault extinguish. The first attempt to recover is a delayed autoreclosure
made a few seconds later. Then, the autoreclose function SDARREC gives a command
signal to the synch-check function to close the circuit breaker A. SECRSYN performs an
energizing check, as the line AB is de-energized (
V_BUS
>
Live bus value
,
V_LINE
<
Dead line value
). After verifying the line AB is dead and the energizing direction is
correct, the relay energizes the line (
V_BUS
->
V_LINE
) by closing the circuit breaker A.
The
PLC
of the power plant discovers that the line has been energized and sends a signal
to the other synch-check function to close the circuit breaker B. Since both sides of the
circuit breaker B are live (
V_BUS
>
Live bus value
,
V_LINE
>
Live bus value
), the
synch-check function controlling the circuit breaker B performs a synch-check and, if the
network and the generator are in synchronism, closes the circuit breaker.
Figure 175:
Synch-check function SECRSYN checking energizing conditions and
synchronism
Connections
A special attention is paid to the connection of the relay. Further, it is checked that the
primary side wiring is correct.
A faulty wiring of the voltage inputs of the relay causes a malfunction in the synch-check
function. If the wires of an energizing input have changed places, the polarity of the input
voltage is reversed (180°). In this case, the relay permits the circuit breaker closing in a
situation where the voltages are in opposite phases. This can damage the electrical devices
in the primary circuit. Therefore, it is extremely important that the wiring from the voltage
transformers to the terminals on the rear of the relay is consistent regarding the energizing
inputs
V_BUS
(bus voltage) and
V_LINE
(line voltage).
The wiring should be verified by checking the reading of the phase difference measured
between the
V_BUS
and
V_LINE
voltages. The phase difference measured by the relay
has to be close to zero within the permitted accuracy tolerances. The measured phase
Содержание RER620
Страница 1: ...Relion Protection and Control Advanced Recloser Protection and Control RER620 Technical Manual ...
Страница 2: ......
Страница 22: ...Section 1MAC309294 MB F 16 RER620 Technical Manual ...
Страница 88: ...Section 3 1MAC309294 MB F Basic functions 82 RER620 Technical Manual ...
Страница 278: ...Section 4 1MAC309294 MB F Protection functions 272 RER620 Technical Manual ...
Страница 362: ...Section 5 1MAC309294 MB F Control functions 356 RER620 Technical Manual ...
Страница 418: ...Section 7 1MAC309294 MB F Measurement functions 412 RER620 Technical Manual ...
Страница 428: ...Section 8 1MAC309294 MB F Recording functions 422 RER620 Technical Manual ...
Страница 464: ...Section 9 1MAC309294 MB F Other functions 458 RER620 Technical Manual ...
Страница 554: ...Section 10 1MAC309294 MB F General function block features 548 RER620 Technical Manual ...
Страница 568: ...Section 12 1MAC309294 MB F Relay physical connections 562 RER620 Technical Manual ...
Страница 574: ...Section 13 1MAC309294 MB F Technical data 568 RER620 Technical Manual ...
Страница 576: ...Section 14 1MAC309294 MB F Relay and functionality tests 570 RER620 Technical Manual ...
Страница 578: ...Section 15 1MAC309294 MB F Applicable standards and regulations 572 RER620 Technical Manual ...
Страница 582: ...Section 16 1MAC309294 MB F Glossary 576 RER620 Technical Manual ...
Страница 583: ......