Section 4
1MAC309294-MB F
Protection functions
126
RER620
Technical Manual
The pickup value multiplication is normally done when the inrush detection function
(INR) is connected to the
ENA_MULT
input.
Timer
Once activated, the timer activates the
PICKUP
output. Depending on the value of the
Operating curve type
setting, the time characteristics are according to DT or IDMT. When
the operation timer has reached the value of
Trip delay time
in the DT mode or the
maximum value defined by the inverse time curve and the
Time added
time has expired,
the
TRIP
output is activated.
When the user programmable IDMT curve is selected, the operate time characteristics are
defined by the parameters
Curve parameter A
,
Curve parameter B
,
Curve parameter C
,
Curve parameter D
and
Curve parameter E
.
If a drop-off situation happens, that is, a fault suddenly disappears before the trip delay is
exceeded, the timer reset state is activated. The functionality of the timer in the reset state
depends on the combination of the
Operating curve type
,
Type of reset curve
and
Reset
delay time
settings. When the DT characteristic is selected, the reset timer runs until the
set
Reset delay time
value is exceeded. When the IDMT curves are selected, the
Type of
reset curve
setting can be set to
“
Immediate
”
,
“
Def time reset
”
or
“
Inverse reset
”
. The
reset curve type “Immediate” causes an immediate reset. With the reset curve type “Def
time reset”, the reset time depends on the
Reset delay time
setting. With the reset curve
type “Inverse reset”, the reset time depends on the current during the drop-off situation. If
the drop-off situation continues, the reset timer is reset and the
PICKUP
output is
deactivated.
The setting
Time multiplier
is used for scaling the IDMT trip and reset times.
The setting parameter
Minimum trip time
defines the minimum desired trip time for IDMT.
The setting is applicable only when the IDMT curves are used.
Do not set the multiplier setting
Pickup value Mult
higher than necessary.
If the value is too high, the function may not trip at all during an inrush
current followed by a non-directional ground fault current, no matter how
severe the fault is.
The relay does not accept the Pickup value or Pickup value Mult setting if
the product of these settings exceeds the Pickup value setting range.
The “Inverse reset” selection is only supported with ANSI or user
programmable types of the IDMT operating curves. If another operating
curve type is selected, an immediate reset occurs during the drop-off
situation.
Содержание RER620
Страница 1: ...Relion Protection and Control Advanced Recloser Protection and Control RER620 Technical Manual ...
Страница 2: ......
Страница 22: ...Section 1MAC309294 MB F 16 RER620 Technical Manual ...
Страница 88: ...Section 3 1MAC309294 MB F Basic functions 82 RER620 Technical Manual ...
Страница 278: ...Section 4 1MAC309294 MB F Protection functions 272 RER620 Technical Manual ...
Страница 362: ...Section 5 1MAC309294 MB F Control functions 356 RER620 Technical Manual ...
Страница 418: ...Section 7 1MAC309294 MB F Measurement functions 412 RER620 Technical Manual ...
Страница 428: ...Section 8 1MAC309294 MB F Recording functions 422 RER620 Technical Manual ...
Страница 464: ...Section 9 1MAC309294 MB F Other functions 458 RER620 Technical Manual ...
Страница 554: ...Section 10 1MAC309294 MB F General function block features 548 RER620 Technical Manual ...
Страница 568: ...Section 12 1MAC309294 MB F Relay physical connections 562 RER620 Technical Manual ...
Страница 574: ...Section 13 1MAC309294 MB F Technical data 568 RER620 Technical Manual ...
Страница 576: ...Section 14 1MAC309294 MB F Relay and functionality tests 570 RER620 Technical Manual ...
Страница 578: ...Section 15 1MAC309294 MB F Applicable standards and regulations 572 RER620 Technical Manual ...
Страница 582: ...Section 16 1MAC309294 MB F Glossary 576 RER620 Technical Manual ...
Страница 583: ......