Section 5
1MAC309294-MB F
Control functions
352
RER620
Technical Manual
5.4.7
Settings
Table 320: DLCM group settings
Parameter
Values (Range)
Unit
Step Default
Description
Operation
1=ON
0=OFF
1=OFF
Operation on/off of loop control
LCM mode
1=Sectionalizer
2=Mid point
3=Tie point
4=Disabled
4=Disabled
Loop control functionality operating mode based on the recloser
type
Dead bus threshold
0.001 … 2.000
xVn
1.000
Voltage level setting (RMS line to neutral) for detecting dead bus
Live bus threshold
0.001 … 2.000
xVn
1.000
Voltage level setting (RMS line to neutral) for detecting live bus.
Dead bus time
1…600
seconds
5
Time duration that voltage should be below the threshold to
determine the bus is dead.
Live bus time
1…600
seconds
5
Time duration that voltage should be above the threshold to
determine the bus is live.
Volt regain time
0…5
seconds
0
When the voltage is lost on a line and the deadbus time is
running, if the voltage comes back above the live bus threshold
for this amount of time, the dead bus timer will reset.
Line side src
1=S1
2=S2
1=S1
Line side source
Vt config line
1 … 3
3
Number of Voltage channels on line side
Vt config load
1 … 3
3
Number of Voltage channels on load side
Vt line enable
1=TRUE
0=FALSE
0=FALSE
To include the voltages on line side for making decisions
Vt load enable
1=TRUE
0=FALSE
0=FALSE
To include the voltages on load side for making decisions
Vt line phase
0=PhA
1=PhB
2=PhC
0=PhA
The connected phase if one voltage channel is used in line side.
Vt load phase
0=PhA
1=PhB
2=PhC
0=PhA
If one voltage channel is used in load side which phase is
connected
Sect3POpmode
0=All Phase
1=Any Phase
1=Any
Phase
Single or three phase operational mode (valid only in
sectionalizing mode)
En set grp chg
1=TRUE
0=FALSE
0=FALSE
Setting group switching is enabled (Valid for Tie point and mid
point mode only)
Reset on power up
1=TRUE
0=FALSE
0=FALSE
Reset on power up setting (valid only in sectionalizing and
midpoint modes)
Sectionalizing reset
1=TRUE
0=FALSE
0=FALSE
Automatic resetting of loop control in sectionalizing mode
SWOTF time
0….120
seconds
5
Switch on to fault time to operate the mid point recloser in lock out
mode or non reclose mode after the loop control sequence is
initiated.
Содержание RER620
Страница 1: ...Relion Protection and Control Advanced Recloser Protection and Control RER620 Technical Manual ...
Страница 2: ......
Страница 22: ...Section 1MAC309294 MB F 16 RER620 Technical Manual ...
Страница 88: ...Section 3 1MAC309294 MB F Basic functions 82 RER620 Technical Manual ...
Страница 278: ...Section 4 1MAC309294 MB F Protection functions 272 RER620 Technical Manual ...
Страница 362: ...Section 5 1MAC309294 MB F Control functions 356 RER620 Technical Manual ...
Страница 418: ...Section 7 1MAC309294 MB F Measurement functions 412 RER620 Technical Manual ...
Страница 428: ...Section 8 1MAC309294 MB F Recording functions 422 RER620 Technical Manual ...
Страница 464: ...Section 9 1MAC309294 MB F Other functions 458 RER620 Technical Manual ...
Страница 554: ...Section 10 1MAC309294 MB F General function block features 548 RER620 Technical Manual ...
Страница 568: ...Section 12 1MAC309294 MB F Relay physical connections 562 RER620 Technical Manual ...
Страница 574: ...Section 13 1MAC309294 MB F Technical data 568 RER620 Technical Manual ...
Страница 576: ...Section 14 1MAC309294 MB F Relay and functionality tests 570 RER620 Technical Manual ...
Страница 578: ...Section 15 1MAC309294 MB F Applicable standards and regulations 572 RER620 Technical Manual ...
Страница 582: ...Section 16 1MAC309294 MB F Glossary 576 RER620 Technical Manual ...
Страница 583: ......