Section 4
1MAC309294-MB F
Protection functions
142
RER620
Technical Manual
The setting parameter
Minimum trip time
defines the minimum desired trip time for IDMT.
The setting is applicable only when the IDMT curves are used.
The timer calculates the pickup duration (PICKUP_DUR) value which indicates the
percentage ratio of the pickup situation and the set trip time. The value is available through
the Monitored data view.
Blocking logic
There are three operation modes in the blocking functionality. The operation modes are
controlled by the
BLOCK
input and the global setting “
Configuration/System/
Blocking
mode”
which selects the blocking mode. The
BLOCK
input can be controlled by a binary
input, a horizontal communication input or an internal signal of the relay program. The
influence of the
BLOCK
signal activation is preselected with the global setting
Blocking
mode
.
The
Blocking mode
setting has three blocking methods. In the “Freeze timers” mode, the
trip timer is frozen to the prevailing value. In the “Block all” mode, the whole function is
blocked and the timers are reset. In the “Block TRIP output” mode, the function operates
normally but the
TRIP
output is not activated.
4.1.4.5
Directional ground-fault principles
In many cases it is difficult to achieve selective ground-fault protection based on the
magnitude of zero sequence current only. To obtain a selective ground-fault protection
scheme, it is necessary to take the phase angle of I
0
into account. This is done by
comparing the phase angle of I
0
to that of the zero sequence voltage (-V
0
).
Relay characteristic angle
The
Characteristic angle
, also known as Relay Characteristic Angle (RCA), Relay Base
Angle or Maximum Torque Angle (MTA), is used in the “Phase angle” mode to turn the
directional characteristic, if the expected fault current angle does not coincide with the
polarizing quantity to produce the maximum torque. That is, RCA is the angle between the
maximum torque line and polarizing quantity. If the polarizing quantity is in phase with
the maximum torque line, RCA is 0 degrees. The angle is positive if operating current lags
the polarizing quantity and negative if it leads the polarizing quantity.
Example 1.
The “Phase angle” mode is selected, compensated network (φRCA = 0 deg)
=>
Characteristic angle
= 0 deg
The
Minimum trip time
setting should be used with great care because the
operation time is according to the IDMT curve, but always at least the value
of the
Minimum operate time
setting. For more information, see the
General function block features section in this manual.
Содержание RER620
Страница 1: ...Relion Protection and Control Advanced Recloser Protection and Control RER620 Technical Manual ...
Страница 2: ......
Страница 22: ...Section 1MAC309294 MB F 16 RER620 Technical Manual ...
Страница 88: ...Section 3 1MAC309294 MB F Basic functions 82 RER620 Technical Manual ...
Страница 278: ...Section 4 1MAC309294 MB F Protection functions 272 RER620 Technical Manual ...
Страница 362: ...Section 5 1MAC309294 MB F Control functions 356 RER620 Technical Manual ...
Страница 418: ...Section 7 1MAC309294 MB F Measurement functions 412 RER620 Technical Manual ...
Страница 428: ...Section 8 1MAC309294 MB F Recording functions 422 RER620 Technical Manual ...
Страница 464: ...Section 9 1MAC309294 MB F Other functions 458 RER620 Technical Manual ...
Страница 554: ...Section 10 1MAC309294 MB F General function block features 548 RER620 Technical Manual ...
Страница 568: ...Section 12 1MAC309294 MB F Relay physical connections 562 RER620 Technical Manual ...
Страница 574: ...Section 13 1MAC309294 MB F Technical data 568 RER620 Technical Manual ...
Страница 576: ...Section 14 1MAC309294 MB F Relay and functionality tests 570 RER620 Technical Manual ...
Страница 578: ...Section 15 1MAC309294 MB F Applicable standards and regulations 572 RER620 Technical Manual ...
Страница 582: ...Section 16 1MAC309294 MB F Glossary 576 RER620 Technical Manual ...
Страница 583: ......