1MAC309294-MB F
Section 8
Recording functions
RER620
421
Technical Manual
Table 379: Non-group analog channel settings for digital fault recorder
Table 380: Non-group binary channel settings for digital fault recorder
Table 381: Control data for digital fault recorder
8.1.6
Monitored data
Table 382: Monitored data for digital fault recorder
Parameter
Values (Range)
Unit Step
Default
Description
Operation
1=on
5=off
1
1=on
Analog channel is enabled or disabled.
Channel selection
1 = IA
2 = IB
3 = IC
4 = IG
5 = VA
6 = VB
7 = VC
8 = VA2
9 = VB2
10 = VC2
11 = Disabled
12 = Disabled
0
0=Disabled
Select the signal to be recorded by this channel. Applicable values
for this parameter are product variant dependent. Every product
variant includes only the values that are applicable to that particular
variant
Channel id text
0 to 64
characters,
alphanumeric
DR analog
channel X
Identification text for the analog channel used in the COMTRADE
format
High trigger level
0.00...60.00
pu
0.01
10.00
High trigger level for the analog channel
Low trigger level
0.00...2.00
pu
0.01
0.00
Low trigger level for the analog channel
Storage mode
0=Waveform
1=Trend / cycle
1
0
Storage mode for the analog channel
Parameter
Values (Range)
Unit Step Default
Description
Operation
1=on
5=off
1
5=off
Binary channel is enabled or disabled
Level trigger mode
1=Positive or Rising
2=Negative or Falling
3=Both
4=Level trigger off
1
1=Rising
Level trigger mode for the binary channel
Storage mode
0=Waveform
1=Trend / cycle
1
0
Storage mode for the binary channel
Channel id text
0 to 64 characters, alphanumeric
DR binary
channel X
Identification text for the analog channel used in the
COMTRADE format
Parameter
Values (Range) Unit Step Default Description
Trig recording
0=Cancel
1=Trig
Trigger the disturbance recording
Clear recordings
0=Cancel
1=Clear
Clear all recordings currently in memory
Parameter
Values (Range) Unit Step Default Description
Number of recordings
0...100
Number of recordings currently in memory
Rem. amount of rec.
0...100
Remaining amount of recordings that fit into the available recording memory,
when current settings are used
Rec. memory used
0...100
%
Storage mode for the binary channel
Time to trigger
0...604 800
s
Time remaining to the next periodic triggering
Содержание RER620
Страница 1: ...Relion Protection and Control Advanced Recloser Protection and Control RER620 Technical Manual ...
Страница 2: ......
Страница 22: ...Section 1MAC309294 MB F 16 RER620 Technical Manual ...
Страница 88: ...Section 3 1MAC309294 MB F Basic functions 82 RER620 Technical Manual ...
Страница 278: ...Section 4 1MAC309294 MB F Protection functions 272 RER620 Technical Manual ...
Страница 362: ...Section 5 1MAC309294 MB F Control functions 356 RER620 Technical Manual ...
Страница 418: ...Section 7 1MAC309294 MB F Measurement functions 412 RER620 Technical Manual ...
Страница 428: ...Section 8 1MAC309294 MB F Recording functions 422 RER620 Technical Manual ...
Страница 464: ...Section 9 1MAC309294 MB F Other functions 458 RER620 Technical Manual ...
Страница 554: ...Section 10 1MAC309294 MB F General function block features 548 RER620 Technical Manual ...
Страница 568: ...Section 12 1MAC309294 MB F Relay physical connections 562 RER620 Technical Manual ...
Страница 574: ...Section 13 1MAC309294 MB F Technical data 568 RER620 Technical Manual ...
Страница 576: ...Section 14 1MAC309294 MB F Relay and functionality tests 570 RER620 Technical Manual ...
Страница 578: ...Section 15 1MAC309294 MB F Applicable standards and regulations 572 RER620 Technical Manual ...
Страница 582: ...Section 16 1MAC309294 MB F Glossary 576 RER620 Technical Manual ...
Страница 583: ......