Example 2
There are two separate sequences implemented with three shots. Shot 1 is implemented by
CBB1 and it is initiated with the high stage of the overcurrent protection (50P-1). Shot 1
is set as a high-speed autoreclosing with a short time delay. Shot 2 is implemented with
CBB2 and meant to be the first shot of the autoreclose sequence initiated by the low stage
of the overcurrent protection (51P) and the low stage of the non-directional ground-fault
protection (51N/G). It has the same reclose time in both situations. It is set as a high-speed
autoreclosing for corresponding faults. The third shot, which is the second shot in the
autoreclose sequence initiated by 51P or 51N/G, is set as a delayed autoreclosing and
executed after an unsuccessful high-speed autoreclosing of a corresponding sequence.
Figure 164:
Autoreclose sequence with two shots with different shot settings
according to initiation signal
t
HSAR
Time delay of high-speed autoreclosing, here:
First reclose time
t
DAR
Time delay of delayed autoreclosing, here:
Second reclose time
t
l>>
Operating time for the 50P-1 protection stage to clear the fault
t
l>
or
lo>
Operating time for the 51P or 51N/G protection stage to clear the fault
t
CB_O
Operating time for opening the circuit breaker
t
CB_C
Operating time for closing the circuit breaker
In this case, the number of needed CBBs is three, that is, the first shot's reclosing time
depends on the initiation signal. The CBB sequence is as follows:
Содержание RER620
Страница 1: ...Relion Protection and Control Advanced Recloser Protection and Control RER620 Technical Manual ...
Страница 2: ......
Страница 22: ...Section 1MAC309294 MB F 16 RER620 Technical Manual ...
Страница 88: ...Section 3 1MAC309294 MB F Basic functions 82 RER620 Technical Manual ...
Страница 278: ...Section 4 1MAC309294 MB F Protection functions 272 RER620 Technical Manual ...
Страница 362: ...Section 5 1MAC309294 MB F Control functions 356 RER620 Technical Manual ...
Страница 418: ...Section 7 1MAC309294 MB F Measurement functions 412 RER620 Technical Manual ...
Страница 428: ...Section 8 1MAC309294 MB F Recording functions 422 RER620 Technical Manual ...
Страница 464: ...Section 9 1MAC309294 MB F Other functions 458 RER620 Technical Manual ...
Страница 554: ...Section 10 1MAC309294 MB F General function block features 548 RER620 Technical Manual ...
Страница 568: ...Section 12 1MAC309294 MB F Relay physical connections 562 RER620 Technical Manual ...
Страница 574: ...Section 13 1MAC309294 MB F Technical data 568 RER620 Technical Manual ...
Страница 576: ...Section 14 1MAC309294 MB F Relay and functionality tests 570 RER620 Technical Manual ...
Страница 578: ...Section 15 1MAC309294 MB F Applicable standards and regulations 572 RER620 Technical Manual ...
Страница 582: ...Section 16 1MAC309294 MB F Glossary 576 RER620 Technical Manual ...
Страница 583: ......