Section 5
1MAC309294-MB F
Control functions
326
RER620
Technical Manual
• The measured line and bus voltages are higher than set values of
Live bus value
and
Live line value
(ENERG_STATE equals to
“
Both Live
”
).
• The measured bus and line frequency are both within the range of 95 to 105 percent
of the value of f
n
.
• The measured voltages for the line and bus are less than set value of
Max energizing
V
.
In case
Synch check mode
is set to “Synchronous”, the additional conditions must be
fulfilled:
• In the synchronous mode, the closing is attempted so that the phase difference at
closing is close to zero.
• The synchronous mode is only possible when the frequency slip is below 0.1 percent
of the value of f
n
.
• The voltage difference must not exceed the 1 percent of the value of VV
n
.
In case
Synch check mode
is set to “Asynchronous”, the additional conditions must be
fulfilled:
• The measured difference of the voltages is less than the set value of
Difference
voltage
.
• The measured difference of the phase angles is less than the set value of
Difference
angle
.
• The measured difference in frequency is less than the set value of
Frequency
difference
.
• The estimated breaker closing angle is decided to be less than the set value of
Difference angle
.
Figure 168:
Conditions to be fulfilled when detecting synchronism between systems
When the frequency, phase angle and voltage conditions are fulfilled, the duration of the
synchronism conditions is checked so as to ensure that they are still met when the
condition is determined on the basis of the measured frequency and phase difference.
Depending on the circuit breaker and the closing system, the delay from the moment the
closing signal is given until the circuit breaker finally closes is about 50 - 250 ms. The
selected
Closing time of CB
informs the function how long, the conditions have to persist.
The synch-check function compensates for the measured slip frequency and the circuit
Содержание RER620
Страница 1: ...Relion Protection and Control Advanced Recloser Protection and Control RER620 Technical Manual ...
Страница 2: ......
Страница 22: ...Section 1MAC309294 MB F 16 RER620 Technical Manual ...
Страница 88: ...Section 3 1MAC309294 MB F Basic functions 82 RER620 Technical Manual ...
Страница 278: ...Section 4 1MAC309294 MB F Protection functions 272 RER620 Technical Manual ...
Страница 362: ...Section 5 1MAC309294 MB F Control functions 356 RER620 Technical Manual ...
Страница 418: ...Section 7 1MAC309294 MB F Measurement functions 412 RER620 Technical Manual ...
Страница 428: ...Section 8 1MAC309294 MB F Recording functions 422 RER620 Technical Manual ...
Страница 464: ...Section 9 1MAC309294 MB F Other functions 458 RER620 Technical Manual ...
Страница 554: ...Section 10 1MAC309294 MB F General function block features 548 RER620 Technical Manual ...
Страница 568: ...Section 12 1MAC309294 MB F Relay physical connections 562 RER620 Technical Manual ...
Страница 574: ...Section 13 1MAC309294 MB F Technical data 568 RER620 Technical Manual ...
Страница 576: ...Section 14 1MAC309294 MB F Relay and functionality tests 570 RER620 Technical Manual ...
Страница 578: ...Section 15 1MAC309294 MB F Applicable standards and regulations 572 RER620 Technical Manual ...
Страница 582: ...Section 16 1MAC309294 MB F Glossary 576 RER620 Technical Manual ...
Страница 583: ......