1MAC309294-MB F
Section 12
Relay physical connections
RER620
559
Technical Manual
Table 433: EIA-232 and EIA-485 jumper connectors for COM1
To ensure fail-safe operation, the bus is to be biased at one end using the pull-up and
pull-down resistors on the communication module. In the 4-wire connection, the pull-up
and pull-down resistors are selected by setting jumpers X5, X6, X8, X9 to enabled
position. The bus termination is selected by setting jumpers X7, X11 to enabled position.
The jumpers have been set to no termination and no biasing as default.
Table 434: 2-wire EIA-485 jumper connectors for COM1
Table 435: 4–wire EIA-485 jumper connectors for COM1
COM2 port connection can be either EIA-485 or optical ST. Connection type is selected
by setting jumpers X27 and X28.
Group
Jumper connection
Description
X19
1-2
2-3
EIA-485
EIA-232
X20
1-2
2-3
EIA-485
EIA-232
X21
1-2
2-3
EIA-485
EIA-232
X26
1-2
2-3
EIA-485
EIA-232
Group
Jumper connection
Description
Notes
X5
1-2
2-3
A+ bias enabled
A+ bias disabled
1
1. Default setting
COM1
Rear connector X6
2-wire connection
X6
1-2
2-3
B- bias enabled
B- bias disabled
X7
1-2
2-3
Bus termination
enabled
Bus termination
disabled
Group
Jumper connection
Description
Notes
X5
1-2
2-3
A+ bias enabled
A+ bias disabled
1
1. Default setting
COM1
Rear connector X6
4-wire TX channel
X6
1-2
2-3
B- bias enabled
B- bias disabled
X7
1-2
2-3
Bus termination enabled
Bus termination disabled
X9
1-2
2-3
A+ bias enabled
A+ bias disabled
4-wire RX channel
X8
1-2
2-3
B- bias enabled
B- bias disabled
X11
1-2
2-3
Bus termination enabled
Bus termination disabled
Содержание RER620
Страница 1: ...Relion Protection and Control Advanced Recloser Protection and Control RER620 Technical Manual ...
Страница 2: ......
Страница 22: ...Section 1MAC309294 MB F 16 RER620 Technical Manual ...
Страница 88: ...Section 3 1MAC309294 MB F Basic functions 82 RER620 Technical Manual ...
Страница 278: ...Section 4 1MAC309294 MB F Protection functions 272 RER620 Technical Manual ...
Страница 362: ...Section 5 1MAC309294 MB F Control functions 356 RER620 Technical Manual ...
Страница 418: ...Section 7 1MAC309294 MB F Measurement functions 412 RER620 Technical Manual ...
Страница 428: ...Section 8 1MAC309294 MB F Recording functions 422 RER620 Technical Manual ...
Страница 464: ...Section 9 1MAC309294 MB F Other functions 458 RER620 Technical Manual ...
Страница 554: ...Section 10 1MAC309294 MB F General function block features 548 RER620 Technical Manual ...
Страница 568: ...Section 12 1MAC309294 MB F Relay physical connections 562 RER620 Technical Manual ...
Страница 574: ...Section 13 1MAC309294 MB F Technical data 568 RER620 Technical Manual ...
Страница 576: ...Section 14 1MAC309294 MB F Relay and functionality tests 570 RER620 Technical Manual ...
Страница 578: ...Section 15 1MAC309294 MB F Applicable standards and regulations 572 RER620 Technical Manual ...
Страница 582: ...Section 16 1MAC309294 MB F Glossary 576 RER620 Technical Manual ...
Страница 583: ......