Section 4
1MAC309294-MB F
Protection functions
238
RER620
Technical Manual
Figure 109:
Retrip logic internal design
The retrip function operates with or without a current check selected with the
CB fail retrip
mode
setting. In
“
Current check
”
mode, the retrip is only performed if the current through
the circuit breaker exceeds the
Current value
level. In “Without check” mode, the retrip is
done without checking the phase currents.
The
CB failure mode
setting is used to select the mode the breaker fault is detected with.
In “Current” mode, the detection is based on the current level exceeding. In “Breaker
status” mode, the detection is based on the closed position of the circuit breaker after a trip
signal is issued, that is, after a long duration of the trip signal. In “Both” mode, the
detection is based either on the exceeding of
Current value
level or on the long duration
of the trip signal. When external information of a circuit breaker fault is connected to the
active
CB_FAULT
input, the retrip function is not allowed to trip. The blocking is used to
disable the whole function.
Back-up trip logic
The operation of the back-up trip logic can be described by using a module diagram when
three phase operation mode is selected:
Содержание RER620
Страница 1: ...Relion Protection and Control Advanced Recloser Protection and Control RER620 Technical Manual ...
Страница 2: ......
Страница 22: ...Section 1MAC309294 MB F 16 RER620 Technical Manual ...
Страница 88: ...Section 3 1MAC309294 MB F Basic functions 82 RER620 Technical Manual ...
Страница 278: ...Section 4 1MAC309294 MB F Protection functions 272 RER620 Technical Manual ...
Страница 362: ...Section 5 1MAC309294 MB F Control functions 356 RER620 Technical Manual ...
Страница 418: ...Section 7 1MAC309294 MB F Measurement functions 412 RER620 Technical Manual ...
Страница 428: ...Section 8 1MAC309294 MB F Recording functions 422 RER620 Technical Manual ...
Страница 464: ...Section 9 1MAC309294 MB F Other functions 458 RER620 Technical Manual ...
Страница 554: ...Section 10 1MAC309294 MB F General function block features 548 RER620 Technical Manual ...
Страница 568: ...Section 12 1MAC309294 MB F Relay physical connections 562 RER620 Technical Manual ...
Страница 574: ...Section 13 1MAC309294 MB F Technical data 568 RER620 Technical Manual ...
Страница 576: ...Section 14 1MAC309294 MB F Relay and functionality tests 570 RER620 Technical Manual ...
Страница 578: ...Section 15 1MAC309294 MB F Applicable standards and regulations 572 RER620 Technical Manual ...
Страница 582: ...Section 16 1MAC309294 MB F Glossary 576 RER620 Technical Manual ...
Страница 583: ......