Section 4
1MAC309294-MB F
Protection functions
166
RER620
Technical Manual
Table 177: 67/51N and 67/50N-1 Non group settings
Operation mode
1=Phase angle
2=IoSin
3=IoCos
4=Phase angle 80
5=Phase angle 88
1=Phase angle
Operation criteria
Characteristic angle
-179...180
deg
1
-90
Characteristic angle
Max forward angle
0...180
deg
1
88
Maximum phase angle in forward direction
Max reverse angle
0...180
deg
1
88
Maximum phase angle in reverse direction
Min forward angle
0...180
deg
1
88
Minimum phase angle in forward direction
Min reverse angle
0...180
deg
1
88
Minimum phase angle in reverse direction
Voltage pickup value
0.010...1.000
xVn
0.001
0.010
Voltage pickup value
Enable voltage limit
0=False
1=True
1=True
Enable voltage limit
Parameter
Values (Range)
Unit
Step
Default
Description
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=Enable
5=Disable
5=Disable
Operation Disable / Enable
Reset delay time
0...60000
ms
1
20
Reset delay time
Minimum trip time
60...60000
ms
1
60
Minimum trip time for IDMT curves
Allow Non Dir
0=False
1=True
0=False
Allows prot activation as non-dir when dir info is invalid
Measurement mode
1=RMS
2=DFT
3=Peak-to-Peak
2=DFT
Selects used measurement mode
Min trip current
0.005...1.000
xIn
0.001
0.005
Minimum trip current
Min trip voltage
0.01...1.00
xVn
0.01
0.01
Minimum trip voltage
Correction angle
0.0...10.0
deg
0.1
0.0
Angle correction
Pol reversal
0=False
1=True
0=False
Rotate polarizing quantity
Curve parameter A
0.0086...120.0000
28.2000
Parameter A for customer programmable curve
Curve parameter B
0.0000...0.7120
0.1217
Parameter B for customer programmable curve
Curve parameter C
0.02...2.00
2.00
Parameter C for customer programmable curve
Curve parameter D
0.46...30.00
29.10
Parameter D for customer programmable curve
Curve parameter E
0.0...1.0
1.0
Parameter E for customer programmable curve
Io signal Sel
1=IG
2=I0
1=IG
Selection for used Io signal
Pol signal Sel
1=Measured VG
2=Calculated V0
3=Neg. seq. volt.
2=Calculated V0
Selection for used polarization signal
Содержание RER620
Страница 1: ...Relion Protection and Control Advanced Recloser Protection and Control RER620 Technical Manual ...
Страница 2: ......
Страница 22: ...Section 1MAC309294 MB F 16 RER620 Technical Manual ...
Страница 88: ...Section 3 1MAC309294 MB F Basic functions 82 RER620 Technical Manual ...
Страница 278: ...Section 4 1MAC309294 MB F Protection functions 272 RER620 Technical Manual ...
Страница 362: ...Section 5 1MAC309294 MB F Control functions 356 RER620 Technical Manual ...
Страница 418: ...Section 7 1MAC309294 MB F Measurement functions 412 RER620 Technical Manual ...
Страница 428: ...Section 8 1MAC309294 MB F Recording functions 422 RER620 Technical Manual ...
Страница 464: ...Section 9 1MAC309294 MB F Other functions 458 RER620 Technical Manual ...
Страница 554: ...Section 10 1MAC309294 MB F General function block features 548 RER620 Technical Manual ...
Страница 568: ...Section 12 1MAC309294 MB F Relay physical connections 562 RER620 Technical Manual ...
Страница 574: ...Section 13 1MAC309294 MB F Technical data 568 RER620 Technical Manual ...
Страница 576: ...Section 14 1MAC309294 MB F Relay and functionality tests 570 RER620 Technical Manual ...
Страница 578: ...Section 15 1MAC309294 MB F Applicable standards and regulations 572 RER620 Technical Manual ...
Страница 582: ...Section 16 1MAC309294 MB F Glossary 576 RER620 Technical Manual ...
Страница 583: ......