1MAC309294-MB F
Section 9
Other functions
RER620
435
Technical Manual
9.1.8
Monitored data
Table 390: Monitored data for UPS
Parameter
Values (Range)
Unit
Step
Default Description
Battery V
0...255
Vdc
1
Battery voltage
Battery charge I
0...2.50
Amp
0.01
Battery charge current Amps
Temperature
-70...+150
°C
1
UPS temperature in degrees Celsius.
AC Input V
1...400
Vac
1
AC input voltage to UPS. For a UPS powered by
DC, this value will be zero.
AC_LOSS
0 = false
1 = true (AC is OK)
bin
1
Indication of Loss of AC
Aux Status
0 = off
1 = on
bin
1
0=off
Indicates if the AUX supply is on/off
Aux voltage
1 = 24V
0 = 12V
bin
1
0=12V
Value of Aux voltage
Aux Load I
0...4.00
Amp
0.01
Value of Aux current
AUX Protection
0 = Normal Operation
1 = In shutdown caused by Short
Time Over Current
2 = In shutdown caused by Long
Time Over Current
3 = In shutdown caused by 60vdc
rail too low (less then 35vdc)
Internal Rail 12V
0...2
Vdc
0.1
12V rail voltage
Internal Rail 60V
0...255
Vdc
1
60V rail voltage
Boost voltage
0...255
Vdc
1
Boost voltage
Battery execution result
0 = Ready for battery test
1 = Battery test is registered
2 = Battery interrupt for PWM3 is
now enabled and is used as a timer
3 = Battery test in process (lasts
about 0.075 second during which
Boost and Battery Charge
functions are disabled
4 = Battery test in process, and
measurements are being taking
(lasts about 0.025 second
5 = Battery test has been
completed for 25 milliseconds, now
take non-test battery voltage
6 = In cool-down period
7 = 60VDC rail voltage too low to
test
8 = Within ten seconds of reset
(must be at least 10 seconds out of
reset to start battery test)
UPS Relay status
0 = off
1 = on
bin
1
Battery UPS status is on/off
Heater switch
0 = off
1 = on
bin
1
Heater switch is on/off
Days since reset
0...1240
day
1
Time that has passed since the last reset. This
timer will rollover if the UPS operates 3.4 years
without a reset.
Hours since reset
0...24
hour
1
See above
Minutes since reset
0...60
min
1
See above
Содержание RER620
Страница 1: ...Relion Protection and Control Advanced Recloser Protection and Control RER620 Technical Manual ...
Страница 2: ......
Страница 22: ...Section 1MAC309294 MB F 16 RER620 Technical Manual ...
Страница 88: ...Section 3 1MAC309294 MB F Basic functions 82 RER620 Technical Manual ...
Страница 278: ...Section 4 1MAC309294 MB F Protection functions 272 RER620 Technical Manual ...
Страница 362: ...Section 5 1MAC309294 MB F Control functions 356 RER620 Technical Manual ...
Страница 418: ...Section 7 1MAC309294 MB F Measurement functions 412 RER620 Technical Manual ...
Страница 428: ...Section 8 1MAC309294 MB F Recording functions 422 RER620 Technical Manual ...
Страница 464: ...Section 9 1MAC309294 MB F Other functions 458 RER620 Technical Manual ...
Страница 554: ...Section 10 1MAC309294 MB F General function block features 548 RER620 Technical Manual ...
Страница 568: ...Section 12 1MAC309294 MB F Relay physical connections 562 RER620 Technical Manual ...
Страница 574: ...Section 13 1MAC309294 MB F Technical data 568 RER620 Technical Manual ...
Страница 576: ...Section 14 1MAC309294 MB F Relay and functionality tests 570 RER620 Technical Manual ...
Страница 578: ...Section 15 1MAC309294 MB F Applicable standards and regulations 572 RER620 Technical Manual ...
Страница 582: ...Section 16 1MAC309294 MB F Glossary 576 RER620 Technical Manual ...
Страница 583: ......